Operation principle
1. The Safe torque off activates (the activation switch is opened, or safety relay contacts
open).
2. The STO inputs of the drive control unit de-energize.
3. The control unit cuts off the control voltage from the output IGBTs.
4. The control program generates an indication as defined by parameter
31.22
(see
the firmware manual of the drive.
The parameter selects which indications are given when one or both STO signals
are switched off or lost. The indications also depend on whether the drive is running
or stopped when this occurs.
Note:
This parameter does not affect the operation of the STO function itself. The
STO function will operate regardless of the setting of this parameter: a running drive
will stop upon removal of one or both STO signals, and will not start until both STO
signals are restored and all faults reset.
Note:
The loss of only one STO signal always generates a fault as it is interpreted
as a malfunction of STO hardware or wiring.
5. The motor coasts to a stop (if running). The drive cannot restart while the activation
switch or safety relay contacts are open. After the contacts close, a reset may be
needed (depending on the setting of parameter
31.22
). A new start command is
required to start the drive.
The Safe torque off function 281
Содержание ACQ580-07
Страница 1: ... ABB DRIVES FOR WATER ACQ580 07 Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...4 Update notice ...
Страница 20: ...16 ...
Страница 26: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 22 Safety instructions ...
Страница 32: ...28 ...
Страница 38: ...34 ...
Страница 66: ...62 ...
Страница 69: ...Mechanical installation 65 ...
Страница 73: ... Mechanical installation 69 ...
Страница 75: ...Declaration of Conformity Mechanical installation 71 ...
Страница 108: ...104 ...
Страница 133: ...Electrical installation 129 ...
Страница 134: ...The route of the control cables for frames R10 and R11 is shown below X504 L504 130 Electrical installation ...
Страница 142: ...138 ...
Страница 156: ...152 ...
Страница 162: ...158 ...
Страница 166: ...Replacing the air filters IP54 UL Type 12 Check the air filters and replace if necessary 162 Maintenance ...
Страница 171: ...Maintenance 167 ...
Страница 177: ...3 4 Maintenance 173 ...
Страница 184: ...14 13 15 16 17 Remove the flange 180 Maintenance ...
Страница 187: ...3 4 5 6 Remove the mounting plate Maintenance 183 ...
Страница 189: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 185 ...
Страница 193: ...4 5 3 6 Remove the mounting plate Maintenance 189 ...
Страница 195: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 191 ...
Страница 217: ...Frame R6 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 213 ...
Страница 218: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 214 Technical data ...
Страница 222: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS250 DET A 218 Technical data ...
Страница 223: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 219 ...
Страница 224: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit option F289 220 Technical data ...
Страница 225: ...Frames R6 and R7 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 221 ...
Страница 228: ...Frame R8 Input and motor cable terminal dimensions bottom entry and exit option F289 224 Technical data ...
Страница 231: ...Frames R8 and R9 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 227 ...
Страница 233: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 229 ...
Страница 257: ...13 Dimension drawings Example dimension drawings are shown below Dimension drawings 253 ...
Страница 258: ...Frames R6 and R7 IP21 UL Type 1 254 Dimension drawings ...
Страница 259: ...Frames R6 and R7 B054 IP42 UL Type 1 Filtered Dimension drawings 255 ...
Страница 260: ...Frames R6 and R7 B055 IP54 UL Type 12 256 Dimension drawings ...
Страница 261: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 257 ...
Страница 262: ...Frames R6 and R7 F289 258 Dimension drawings ...
Страница 263: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 259 ...
Страница 264: ...Frames R8 and R9 IP21 UL Type 1 260 Dimension drawings ...
Страница 265: ...Frames R8 and R9 B054 IP42 UL Type 1 Filtered Dimension drawings 261 ...
Страница 266: ...Frames R8 and R9 B055 IP54 UL Type 12 262 Dimension drawings ...
Страница 267: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 263 ...
Страница 268: ...Frames R8 and R9 F289 264 Dimension drawings ...
Страница 269: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 265 ...
Страница 295: ... Declaration of conformity The Safe torque off function 291 ...
Страница 296: ...292 ...
Страница 302: ...298 ...
Страница 309: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 305 ...
Страница 310: ...306 ...
Страница 316: ...312 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...
Страница 322: ...318 ...