ACQ550-U1 User’s Manual
127
3023
WIRING FAULT
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running it monitors for:
• Improper connections of input power to the drive output (the drive can display fault 35,
OUTPUT
WIRING
if improper
connections are detected).
• Ground faults (the drive can display fault 16,
EARTH
FAULT
if a ground fault is detected). Also, see parameter 3017
EARTH
FAULT
.
0 =
DISABLE
– No drive response to either of the above monitoring results.
Note:
Disabling wiring fault (ground fault) may void the warranty.
1 =
ENABLE
– The drive displays faults when this monitoring detects problems.
3024
CB TEMP FAULT
Defines the drive response to control board overheating.
0 =
DISABLE
– No response.
1 =
ENABLE
– Displays fault 37 (
CB
OVERTEMP
) and the drive coasts to stop.
3028
EARTH FAULT LVL
Defines detection level for ground (earth) fault.
Note:
Parameter 3017 EARTH FAULT has to be enabled.
1 =
LOW
– Lower level of ground (earth) current detected generates a fault (high sensitivity). Default setting.
2 =
MEDIUM
– Medium sensitivity to ground (earth) fault current.
3 =
HIGH
– Higher level of ground (earth) current detected generates a fault (low sensitivity).
Code Description
Содержание ACQ550-x1-06A6-2
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...