![ABB ACQ550-x1-06A6-2 Скачать руководство пользователя страница 72](http://html1.mh-extra.com/html/abb/acq550-x1-06a6-2/acq550-x1-06a6-2_user-manual_3541910072.webp)
72
ACQ550-U1 User’s Manual
Parameters
1205
CONST
SPEED
4
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm -U1: 24.0 Hz / 1440 rpm
1206
CONST
SPEED
5
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm -U1: 30.0 Hz / 1800 rpm
1207
CONST
SPEED
6
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm -U1: 48.0 Hz / 2880 rpm
1208
CONST
SPEED
7
0.0…500.0 Hz / 0…30000 rpm
0.1 Hz / 1 rpm -U1: 60.0 Hz / 3600 rpm
1209
TIMED
MODE
SEL
1 =
EXT
/
CS
1/2/3, 2 =
CS
1/2/3/4
1
2 (
CS
1/2/3/4)
Group 13: ANALOG INPUTS
1301
MINIMUM
AI
1 0.0…100.0%
0.1%
0.0%
1302
MAXIMUM
AI
1 0.0…100.0%
0.1%
100.0%
1303
FILTER
AI
1 0.0…10.0 s
0.1 s
0.1 s
1304
MINIMUM
AI
2 0.0…100.0%
0.1%
20.0%
1305
MAXIMUM
AI
2 0.0…100.0%
0.1%
100.0%
1306
FILTER
AI
2 0.0…10.0 s
0.1 s
0.1 s
Group 14: RELAY OUTPUTS
1401
RELAY
OUTPUT
1
0…44, 46, 47, 52
1
1 (
READY
)
1402
RELAY
OUTPUT
2
0…44, 46, 47, 52
1
2 (
RUN
)
1403
RELAY
OUTPUT
3
0…44, 46, 47, 52
1
3 [
FAULT
(-1)]
1404
RO
1
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1405
RO
1
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1406
RO
2
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1407
RO
2
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1408
RO
3
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1409
RO
3
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1410
RELAY
OUTPUT
4
0…44, 46, 47, 52
1
0 (
NOT
SEL
)
1411
RELAY
OUTPUT
5
0…44, 46, 47, 52
1
0 (
NOT
SEL
)
1412
RELAY
OUTPUT
6
0…44, 46, 47, 52
1
0 (
NOT
SEL
)
1413
RO
4
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1414
RO
4
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1415
RO
5
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1416
RO
5
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1417
RO
6
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1418
RO
6
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
Group 15: ANALOG OUTPUTS
1501
AO
1
CONTENT
SEL
99…178
1
102 (parameter 0102
OUTPUT
SPEED
)
1502
AO
1
CONTENT
MIN
-
-
Depends on the signal
selected with par. 1501
1503
AO
1
CONTENT
MAX
-
-
Depends on the signal
selected with par. 1501
1504
MINIMUM
AO
1
0.0…20.0 mA
0.1 mA
0.0 mA
1505
MAXIMUM
AO
1
0.0…20.0 mA
0.1 mA
20.0 mA
1506
FILTER
AO
1
0.0…10.0 s
0.1 s
0.1 s
1507
AO
2
CONTENT
SEL
99…178
1
104 (parameter 0104
CURRENT
)
1508
AO
2
CONTENT
MIN
-
-
Depends on the signal
selected with par. 1507
1509
AO
2
CONTENT
MAX
-
-
Depends on the signal
selected with par. 1507
Code
Name
Range
Resolution
Default
User
S
Содержание ACQ550-x1-06A6-2
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...