ACQ550-U1 User’s Manual
83
Complete parameter descriptions
This section describes the actual signals and parameters for ACQ550.
Group 99: START-UP DATA
This group defines special start-up data required to:
•
set up the drive
•
enter motor information.
Code Description
9901
LANGUAGE
Selects the display language.
9902
APPLIC MACRO
Selects an application macro. Application macros automatically edit parameters to configure the ACQ550 for a
particular application.
-1 =
USER
S
1
SAVE
, -3 =
USER
S
2
SAVE
– With these it is possible to save two different user parameter sets into the
drive permanent memory for later use. Each set contains parameter settings, including
, and the results of the motor identification run.
0 =
USER
S
1
LOAD
, -2 =
USER
S
2
LOAD
– With these the user parameter sets can be taken back in use.
9904
MOTOR CTRL MODE
Selects the motor control mode.
1 or 2 =
VECTOR
:
SPEED
– sensorless vector control mode.
• Reference 1 is speed reference in rpm.
• Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
MAXIMUM
SPEED
, or 2001
MINIMUM
SPEED
if the absolute value of the minimum speed is greater than the maximum
speed).
3 =
SCALAR
:
FREQ
– scalar control mode – Default
• Reference 1 is frequency reference in Hz.
• Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008
MAXIMUM
FREQ
, or 2007
MINIMUM
FREQ
if the absolute value of the minimum speed is greater than the
maximum speed).
9905
MOTOR NOM VOLT
Defines the nominal motor voltage.
• Must equal the value on the motor rating plate.
• The ACQ550 cannot supply the motor with a voltage greater than the input
power (mains) voltage.
9906
MOTOR NOM CURR
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
• Range allowed: 0.2…2.0 ·
I
2hd
(where
I
2hd
is drive current).
9907
MOTOR NOM FREQ
Defines the nominal motor frequency.
• Range: 10…500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals the
MOTOR
NOM
VOLT
.
• Field weakening point = Nom Freq · Supply Volt / Mot Nom Volt
ACQ Control Panel ACQ-CP-AQ:
0 =
ENGLISH
1 =
ENGLISH
(
AM
)
2 =
DEUTSCH
3 =
ITALIANO
4 =
ESPAÑOL
5 =
PORTUGUES
6 =
NEDERLANDS
7 =
FRANÇAIS
8 =
DANSK
9 =
SUOMI
10 =
SVENSKA
11 =
RUSSKI
12 =
POLSKI
13 =
TÜRKÇE
14 =
CZECH
15 =
MAGYAR
16 =
ELLINIKA
17 =
CHINESE
18 =
KOREAN
19 =
JAPANESE
1 =
ABB
2-
WIRE
2 = 3-
WIRE
3 =
ALTERNATE
4 =
MOTOR
POT
5 =
HAND
/
AUTO
6 =
PID
CONTROL
7 =
PFC
CONTROL
0 =
USER
S
1
LOAD
-1 =
USER
S
1
SAVE
-2 =
USER
S
2
LOAD
-3 =
USER
S
2
SAVE
P 9907
P 9905
Output
frequency
Output voltage
Содержание ACQ550-x1-06A6-2
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...