![ABB ACH580-34 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/abb/ach580-34/ach580-34_quick-installation-and-start-up-manual_3045231012.webp)
Measure the insulation resistance of the input and motor
cables and the motor
Before you connect the input power cable to the drive, measure its insulation resistance
according to local regulations.
Ground the motor cable shield at the motor end. For minimal interference, make a
360° grounding at the cable entry, or keep the pig tail short.
Measure the insulation resistance of the motor and motor cable when the motor cable
is disconnected from the drive. Measure the insulation resistance between each phase
conductor and the Protective Earth conductor using a measuring voltage of 1000 V DC.
The insulation resistance of an ABB motor must be greater than 100 Mohm (reference
value at 25 °C or 77 °F). For the insulation resistance of other motors, consult the
manufacturer’s instructions.
Note: Moisture inside the motor casing will reduce the insulation resistance. If you
suspect moisture, dry the motor and repeat the measurement.
1000 V DC,
>
100 Mohm
U1-PE, V1-PE, W1-PE
ohm
M
3~
U1
V1
W1
PE
Install the drive module and LCL filter module into an
enclosure
See
Installing the drive module and LCL filter module into a Rittal VX25
.
Tasks
Step
Mechanical accessories
Attach the plinth to the floor.
1
Attach the enclosure frame to the plinth.
2
Make the bottom plate with 360-degree grounding entries for power cables. Attach the bottom
plate to the enclosure frame.
3
Attach the punched section to the back of enclosure frame.
4
Attach the mounting brackets to the punched section.
5
LCL filter module
Install the pedestal to the LCL filter module.
6
Install the cooling fan to the LCL filter module.
7
Attach the LCL filter module pedestal guide plate to the enclosure bottom plate.
8
Attach the drive module pedestal guide plate to the enclosure bottom plate.
9
Attach the extraction/installation ramp to the LCL filter module pedestal guide plate.
10
To prevent the LCL filter module from falling, attach its lifting lugs with chains to the enclosure
frame.
11
12 EN – Quick installation and start-up guide
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
SV
TR
ZH
Содержание ACH580-34
Страница 2: ......
Страница 44: ...44 ...
Страница 176: ...176 ...
Страница 242: ...242 ...
Страница 264: ...264 ...
Страница 284: ...284 ...
Страница 306: ...306 Step by step drawings for an installation example in Rittal VX25 800 mm wide enclosure ...