Parameter listing and descriptions
181
ACH550-01 User's Manual
0308
ALARM WORD 1
-
Read-only copy of the
ALARM
WORD
1
• When an alarm is active, the corresponding bit for the active alarm is
set in the Alarm Words.
• Each alarm has a dedicated bit allocated within Alarm Words.
• Bits remain set until the whole alarm word is reset. (Reset by writing
zero to the word).
• The control panel displays the word in hex. For example, all zeros
and a 1 in Bit 0 display 0001. All zeros and a 1 in Bit 15 display 8000.
0309
ALARM WORD 2
-
Read-only copy of the
ALARM
WORD
2
• See parameter 0308.
Code Description
Range
Bit # 0308,
ALARM
WORD
1
0309,
ALARM
WORD
2
0
OVERCURRENT
OFF BUTTON
1
OVERVOLTAGE
PID SLEEP
2
UNDERVOLTAGE
ID RUN
3
DIR LOCK
OVERRIDE
4
IO COMM
START ENABLE 1 MISSING
5
AI1 LOSS
START ENABLE 2 MISSING
6
AI2 LOSS
EMERGENCY STOP
7
PANEL LOSS
Reserved
8
DEVICE OVERTEMP
FIRST START
9
MOTOR TEMP
Reserved
10
Reserved
USER LOAD CURVE
11
MOTOR STALL
START DELAY
12
AUTORESET Reserved
13
AUTOCHANGE
14
PFA I LOCK
15
Reserved