268
Parameter listing and descriptions
ACH550-01 User's Manual
3615
STOP TIME 4
Defines timer 4 daily start time.
• See parameter 3603.
3616
START DAY 4
Defines timer 4 weekly start day.
• See parameter 3604.
3617
STOP DAY 4
Defines timer 4 weekly stop day.
• See parameter 3605.
3622
BOOST SEL
-6…6
Selects the source for the boost signal.
0 =
NOT
SEL
– Boost signal is disabled.
1 =
DI
1 – Defines
DI
1 as the boost signal.
2…6 =
DI
2…
DI
6 – Defines
DI
2…
DI
6 as the boost signal.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the boost signal.
-2…-6 = Defines an inverted digital input
DI
2…
DI
6 as the boost signal.
3623
BOOST TIME
00:00:00…23:59:58
Defines the boost ON time. Time is started when
BOOST
SEL
signal is
released. If parameter value is 01:30:00, boost is active for 1 hour and
30 minutes after activation DI is released.
Code Description
Range
Boost active
Activation DI
Boost time
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com