Parameter listing and descriptions
215
ACH550-01 User's Manual
1609
START ENABLE 2
-6…7
Selects the source of the Start enable 2 signal.
Note:
Start enable functionality
differs
from the Run enable
functionality.
0 =
NOT
SEL
– Allows the drive to start without an external Start enable
signal.
1 =
DI
1 – Defines digital input
DI
1 as the Start enable 2 signal.
• This digital input must be activated for Start enable 2 signal.
• If the voltage drops and de-activates this digital input, the drive will
coast to stop and show alarm 2022 on the control panel display. The
drive will not start until the Start enable 2 signal resumes.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the Start enable 2
signal.
• See
DI
1 above.
7 =
COMM
– Assigns the fieldbus Command Word as the source for the
Start enable 2 signal.
• Bit 3 of Command Word 2 (parameter 0302) activates the Start
disable 2 signal.
• See the fieldbus user’s manual for detailed instructions.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the Start enable 2
signal.
-2…-6 =
DI
2 (
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as the Start enable 2 signal.
• See
DI
1 (
INV
) above.
1610
DISPLAY ALARMS
0=NO, 1=YES
Controls the visibility of the following alarms:
• 2001
OVERCURRENT
• 2002
OVERVOLTAGE
• 2003
UNDERVOLTAGE
• 2009
DEVICE
OVERTEMP
For more information, see section
Alarm listing
on page
381
.
0 =
NO
– The above alarms are suppressed.
1 =
YES
– All of the above alarms are enabled.