Chapter 3 – Electrical Installation
3-38
ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
Installation of
Optional Modules
This section gives general installation instructions for the Drive
Window
PC tool and ACx 600 optional modules, such as fieldbus adapters, I/O
extension modules and the pulse encoder interface. Connection
examples are given at the end of the section.
Placement
The module should be installed on the DIN mounting rail inside the
inverter unit cabinet, located on the inside of the left-hand side cabinet
wall. The DIN rail of ACx 6x7 units is located in the Auxiliary Control
Unit (ACU). Follow the instructions given in the
Mechanical Installation
chapter of the module manual.
Power Supply
for the Module
The 24 V d.c. supply for
one
optional module is provided by the NIOC
board of the inverter module (terminal X23). The NIOC board is
assembled into the NDCU control unit, mounted on a DIN rail inside the
inverter unit cabinet or in the Auxiliary Control Unit (ACx 6x7 units).
Fibre Optic Link
Optional modules are connected via a DDCS fibre optic link to the
NAMC board or NDCO board (both mounted on top of the NIOC
board). The terminals to which the cables are connected on the NAMC/
NDCO board are given in the table below. Channel CH1 is on
NAMC-11/51 board. Channels CH0, CH2 and CH3 are on the NDCO
board. The NAMC-03 and NAMC-21/22 boards include channels CH0
to CH3.
The NAMC 11/51 board is used with ACx 6x7 units. The NAMC-21 and
NAMC 22 boards are used with ACS 600 MultiDrive: NAMC-21 with
AC 80 and NAMC 22 with the fieldbus.
* on the NDCO board when the NAMC-11/51 board is used.
1)
Drive
Window
Light is connected via an NPCU RS-232/485 converter to the panel
connector on the cover (or to modular jack X19 on the NAMC-11/51 board).
Module Type
Channel
Terminals
Fieldbus Adapter Modules
CH0*
V13*, V14*
I/O Extension Modules
CH1
V15, V16
Pulse Encoder Interface Module
CH2* with ACS 600
Standard Application
Program 5.x
V17*, V18*
CH1 with ACS 600 System,
Crane Master/Follower and
Template Application
Program
V15, V16
Double Pulse Encoder Interface
Module (for ACP 600 only)
CH2*
V17*, V18*
Drive
Window
1)
CH3*
V19*, V20*
Содержание ACA 6 Series
Страница 4: ......
Страница 8: ...Safety Instructions vi ACS 600 MultiDrive ...
Страница 12: ...x ACS 600 MultiDrive Hardware Manual ...
Страница 26: ...Chapter 1 Introduction 1 14 ACS 600 MultiDrive Hardware Manual ...
Страница 42: ...Chapter 2 Mechanical Installation 2 16 ACA 6xx Sections and ACS ACC 6x7 132 to 3000 kW Frequency Converters ...
Страница 100: ...Chapter 6 Preventive Maintenance 6 6 ACS 600 MultiDrive ...
Страница 101: ......