Chapter 3 – Electrical Installation
ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
3-23
Common Mode Filter
If common mode filter or light common mode filter is required (see
Motor Connections / Requirements Table
in
Safety Instructions)
, lead
the motor cable phase conductors through the toroidal cores as
follows:
1.
Connect the twisted cable screen to the PE terminal.
2.
Wrap the phase conductors together with the silicon rubber tape
delivered with the toroidal cores to provide thermal insulation for
the conductor insulator. Cover the part of the cable which will be
left inside the core(s) + 20 mm below. Approximately 1.5 metres of
tape is needed per cable. Each turn must overlap the previous turn
by half the width of the tape.
3.
Bind the conductors tightly with non-conductive electrical tape and
a heat-resisting non-metallic cable tie in order to prevent
conductor insulation damage caused by the core edges.
4.
Slide the core(s) onto the taped part of the phase conductors.
5.
Bind the cores together and onto the taped part of the phase
conductors with heat-resisting non-metallic cable ties.
Common Mode Filter
Light
Common Mode Filter
2
3
1
5
Code 64315439-B
Содержание ACA 6 Series
Страница 4: ......
Страница 8: ...Safety Instructions vi ACS 600 MultiDrive ...
Страница 12: ...x ACS 600 MultiDrive Hardware Manual ...
Страница 26: ...Chapter 1 Introduction 1 14 ACS 600 MultiDrive Hardware Manual ...
Страница 42: ...Chapter 2 Mechanical Installation 2 16 ACA 6xx Sections and ACS ACC 6x7 132 to 3000 kW Frequency Converters ...
Страница 100: ...Chapter 6 Preventive Maintenance 6 6 ACS 600 MultiDrive ...
Страница 101: ......