Section 1 Introduction
Control Software
3BSE036351-510 A
51
•
Oscillator supervision
•
CRC on firmware and data storage
An SM811 operates like an SM810 for SIL2 but can also together with the PM865
form a controller compliant with SIL3 according to IEC61508, certified by TÜV.
The ModuleBus telegrams used in a High Integrity system with the S800 High
Integrity modules use the concept of long frames. Long frames are ModuleBus
telegrams that are extended with a safety header, comprising additional diagnostics
data and CRC32. S800 ModuleBus telegrams sent to the S800 I/O High Integrity
modules uses data from the PM865 and an inverted CRC32 from the
SM810/SM811. The I/O module checks that the safety header is correct. Data
received from the S800 I/O High Integrity modules over the ModuleBus have the
safety header independently verified by both SM810/SM811 and PM865. Any
CRC32 or other faults in the safety header will result in a retry transmission and, if
repeated, a shutdown of the faulty S800 I/O High Integrity module.
Control Software
The software used by the AC 800M Controller is named Control Software.
This name does not stand for a specific software package; is merely a generic name
for the scope of functions used in a controller. These functions are provided by:
•
Hardware functions (supervision, communication buses, I/O buses)
•
Firmware functions loaded into the controller (real time executive system, real
time clock, redundant communication)
•
Application programs loaded into the controller (library functions,
communication protocols).
To produce an application, it is necessary to use the Control Builder M tool. This
tool is extremely versatile, having many useful functions in addition to system
configuration.
Содержание AC 800M
Страница 1: ...Power and productivity for a better worldTM AC 800M Controller Hardware System Version 5 1...
Страница 2: ......
Страница 3: ...AC 800M Controller Hardware System Version 5 1...
Страница 44: ...PM891 Processor Unit General Section 1 Introduction 44 3BSE036351 510 A Figure 11 Block diagram of PM891...
Страница 150: ...Mounting Dimensions for Proper Ventilation Section 2 Installation 150 3BSE036351 510 A...
Страница 190: ...Verification of Redundant CPU Section 4 Operation 190 3BSE036351 510 A...