Installing the S100 I/O Interface, CI856/TP856
Section 2 Installation
120
3BSE036351-510 A
Installing the S100 I/O Interface, CI856/TP856
The CI856 is powered from the processor unit via the CEX-Bus and requires
therefore no additional external power source.
Use the following procedure to install the CI856/TP856:
1.
Mount the unit on the DIN-rail, see
Mounting AC 800M Units onto DIN-Rail
on page 65 and
Installing the PM86x/TP830 Processor Unit in Single
Configuration
on page 78.
2.
Connect the S100 I/O cable, TK575/TK580, to the contact on the baseplate. A
bus extender, DSBC174/DSBC176/DSBC173A, must be used.
S100 I/O Connection and Installation
Connect the S100 I/O rack cable TK575/TK580 to the “I/O-labeled” 36-pin
centerline miniature ribbon connector located on TP856.
Installation of S100 I/O
For installation of the S100 I/O-related components, see S100 I/O documentation.
Note that there is no unit redundancy for the CI856 unit.