Section 1 Introduction
PM8xx/TP830 Processor Unit – General
3BSE036351-510 A
37
PROFIBUS DP, FOUNDATION Fieldbus H1, FOUNDATION Fieldbus High Speed
Ethernet and dual RS-232C ports are some examples of unit types available for
connection to the CEX-Bus. It is possible to use redundant communication
interfaces, for example PROFIBUS DP.
Figure 6
on page 38 provides examples of various ways to connect the S800 I/O
units. It can be seen, at the top right-hand area of
Figure 6
on page 38, that one
cluster (or group) of units (maximum number of units per cluster is 12) is connected
to the electrical ModuleBus of an AC 800M Controller. However, a further seven
clusters (each comprising up to 12 units) can be added to the optical ModuleBus,
thus achieving a total count of 96 units per AC 800M Controller when using only
the ModuleBus.
To the left on
Figure 6
on page 38, there is a PROFIBUS DP segment. This allows
for a large increase in the numbers of units connected to each AC 800M Controller.
Here the segment is shown as having an FCI unit (type CI801), connected to the
PROFIBUS DP network. The use of FCI units allows the selection of units from
several I/O families.
Figure 7
on page 39 shows another example for I/O units based on a
FOUNDATION Fieldbus High Speed Ethernet (FF HSE).
For further examples refer to the relevant documentation for the I/O system in
question.
Connecting S800 I/O units (using the ModuleBus) to an AC 800M Controller
mounted with a
PM851/PM851A
processor unit is restricted to, one electrical
ModuleBus cluster and one optical ModuleBus cluster.
Содержание AC 800M
Страница 1: ...Power and productivity for a better worldTM AC 800M Controller Hardware System Version 5 1...
Страница 2: ......
Страница 3: ...AC 800M Controller Hardware System Version 5 1...
Страница 44: ...PM891 Processor Unit General Section 1 Introduction 44 3BSE036351 510 A Figure 11 Block diagram of PM891...
Страница 150: ...Mounting Dimensions for Proper Ventilation Section 2 Installation 150 3BSE036351 510 A...
Страница 190: ...Verification of Redundant CPU Section 4 Operation 190 3BSE036351 510 A...