Using PTP for synchronizing the MU
SAM600 VT
SAM600 CT
SAM600 TS
IED
PTP
9-2
IEC17000040-1-en.vsdx
IEC17000040 V1 EN-US
Figure 118:
Setting example with PTP synchronization
Settings on the local HMI under
Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2
:
•
HwSyncSrc
: is not used as the SW-time and HW-time are connected with each
other due to PTP
•
SyncLostMode
: set to
Block
to block protection functions if time
synchronization is lost or set to
BlockOnLostUTC
if the protection functions
are to be blocked when global common synchronization is lost
•
SyncAccLevel
: can be set to
1μs
since this corresponds to a maximum phase
angle error of 0.018 degrees at 50Hz
Settings on the local HMI under
Main menu/Configuration/Communication/
Ethernet configuration/Access point/AP_X
:
•
Operation: On
•
PTP: On
Section 13
1MRK 511 423-UEN A
Station communication
248
Bay control REC650 2.2 IEC
Application manual