110kV Busbar
200/1
35 / 0,1
kV
35kV Busbar
500/5
P
Q
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
U
L1L2
IEC09000040-1-en.vsd
IED
IEC09000040-1-EN V1 EN-US
Figure 99:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure
necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel
PhaseAngleRef
“Setting of the phase reference channel”
) data using PCM600 for
analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
Section 10
1MRK 511 423-UEN A
Monitoring
202
Bay control REC650 2.2 IEC
Application manual