1.
Turn off the power.
2.
Open the seal on the front panel by removing the sealing wire and screw the sealing
screw all the way in.
3.
Lift the handle to 90 degrees to release the latching mechanism.
The unit is pushed about 0.28 inches (7 mm) out of the case and the connectors are
separated.
4.
Pull the unit out of the case.
GUID-A04EACAD-96E1-435A-9E53-D25549F89459 V1 EN
Figure 2:
Detaching a plug-in unit from the case
The IED features an automatic short-circuit mechanism in the CT
connector. Therefore, detaching the plug-in unit will not open the
secondary circuit of the CT which could cause dangerously high voltages.
Do not touch terminals inside the case after removing the plug-in unit.
Live terminals can be inside the case.
Section 4
1MAC457436-IB B
Mounting
12
620 series ANSI
Installation Manual