An IED equipped with optic connections requires a minimum depth of
7.09 inches (180 mm). Check the allowed minimum bending radius from
the optical cable manufacturer.
1.
Loosen the four M5 fixing screws in the case to fit the case into the panel cut-out.
2.
Mount the case to the panel cut-out from the front.
3.
Mount the protection cover from the rear.
1
GUID-5CADE088-6F6B-4C85-94A3-F48F9234F7C2 V1 EN
Figure 20:
Mounting the protection cover
1 Protection cover
4.
Tighten the M5 (T25) screws.
Section 4
1MAC457436-IB B
Mounting
32
620 series ANSI
Installation Manual