96
Chapter 17
Configuration
Manual Corrigo Ventilation, revision R
Alarm text
Pri Description
67
Sensor error Intake temp
B
Malfunction of connected sensor
68
Sensor error Extra sensor 2
B
Malfunction of connected sensor
69
Sensor error Extra sensor 3
B
Malfunction of connected sensor
70
Sensor error Extra sensor 4
B
Malfunction of connected sensor
71
Sensor error Extra sensor 5
B
Malfunction of connected sensor
72
Sensor error Extra SAF
pressure
B
Malfunction of connected sensor
73
Sensor error Extra EAF
pressure
B
Malfunction of connected sensor
77
Alarm frequency converter
SAF
A
Malfunction of frequency converter SAF
78
Alarm frequency converter
EAF
A
Malfunction of frequency converter EAF
79
Communication error
Frequency SAF
C
Communication error Vacon NXL/Lenze
SMV/Omron V1000/Emerson
80
Communication error
Frequency EAF
C
Communication error Vacon NXL/Lenze
SMV/Omron V1000/Emerson
81
Communication error
Expansion unit 1
C
Communication problem with connected
expansion unit
82
Communication error
Expansion unit 2
C
Communication problem with connected
expansion unit
83
Warning Frequency converter
SAF
C
Alarm from frequency converter via
Modbus communication
84
Warning Frequency converter
EAF
C
Alarm from frequency converter via
Modbus communication
85
Output in manual mode
C
Analogue or digital output in manual mode
86
Time for service
C
Time for service
87
Manual Y4-Extra Sequence
control
C
Y4-Extra sequence in manual control
88
Restart blocked after power
on
B
Restart blocked due to earlier power failure
89
Manual Y5-Extra Sequence
control
C
Y5 Extra sequence in manual control
90
Filter guard 2
B
Filter guard pressure switch activated
91
High temp Extra sensor 1
-
High temperature Extra sensor 1
92
Low temp Extra sensor 1
-
Low temperature Extra sensor 1
93
High temp Extra sensor 2
-
High temperature Extra sensor 2
94
Low temp Extra sensor 2
-
Low temperature Extra sensor 2
95
High temp Extra sensor 3
-
High temperature Extra sensor 3
96
Low temp Extra sensor 3
-
Low temperature Extra sensor 3
97
High temp Extra sensor 4
-
High temperature Extra sensor 4
98
Low temp Extra sensor 4
-
Low temperature Extra sensor 4
99
High temp Extra sensor 5
-
High temperature Extra sensor 5
100 Low temp Extra sensor 5
-
Low temperature Extra sensor 5