100
Chapter 17
Configuration
Manual Corrigo Ventilation, revision R
Exch 100% at start
2 sec
Alarm delay at start
60 sec
For the function ”Slave control of the extract air fan”, the fan will start directly at 50 % after the
start delay, in order for the heating of the exchanger to work for this operating mode. When the
supply air fan starts, the extract air fan will be slave controlled by the flow in the supply air duct.
17.30.6 Split controller signal
Splits the controller output (Heating Controller Output signal = HCOut) between the analogue
temperature control output signals Y1, Y2 and Y3 for "Heating", "Heat exchanger" and "Cooling".
To create a neutral zone, leave a percentage gap between sequences.
The set P-band for the supply air controller is for the whole controller signal. This means that the P-
band for each sequence is proportionate to the split percentage values given to sequences.
Example:
P-band for the supply air controller is set to 33K. The HCOut is set so that cooling gets 0…30 % =
30 %, the exchanger gets 32…50 % = 18 % and the heater gets 54…100 % = 46 %. The individual
P-bands will then be:
Chiller: 30 % of 33°C = 10°C
Exchanger: 18 % of 33°C = 6°C
Heating: 46 % of 33°C = 15°C
The remaining 2°C are the neutral zone between cooling and exchanger.
Split settings
Exchanger
0% at HCOut= 32%
100% at HCOut= 50%
Split settings
Heating
0% at HCOut= 54%
100% at HCOut= 100%
Split settings
Cooling
0% at HCOut= 30%
100% at HCOut= 0%
Split settings
Extra Sequence Y4
0% at HCOut= 0%
100% at HCOut= 0%
Split settings
Extra Sequence Y5
0% at HCOut= 0%
100% at HCOut= 0%