Manual Corrigo Ventilation, revision R
Chapter 17
Configuration
83
SAF with EAF slave / EAF with SAF slave
If fan slave operation has been configured, there is a submenu for setting the CAV factor, a factor
which determines the slave fan output in relation to the output of the controlling fan.
SAF/EAF CAV factor:
1.00
For more detailed description, see the section SAF with EAF slave under 5.4.1 Pressure control.
SAF with EAF flow control / EAF with SAF flow control
If fan slave operation and flow control has been configured, there are submenus for setting the flow
calculation factors for "SAF" and "EAF", and the CAV factor for "SAF/EAF".
SAF flow control
factors
K-constant: 100
X-constant: 0.50
EAF flow control
factors
K-constant: 100
X-constant: 0.50
SAF/EAF CAV factor:
1.00
For more detailed description, see the section SAF with EAF flow control / EAF with SAF flow
control under 5.4.1 Pressure control.
Crosswise interlock between fans
Crosswise interlock means that if one of the fans stops running, the other fan will automatically stop
as well.
Crosswise interlock
between SAF and EAF
No
17.5 Extra control circuit
The extra control circuit can be configured to be either constantly active or to be active only when
the regular control circuit is active.
Mode extra unit
Running if
unit runs
The extra control circuit can be configured to be either a heating or a cooling circuit.
Control mode extra
unit:
Heating