76
Chapter 15
Settings
Manual Corrigo Ventilation, revision R
Alarm delay, exchanger efficiency
Low efficiency
30 min
Alarm delay, fan malfunction
Alarm delay malfunc.
SAF: 120 sec
EAF: 120 sec
Alarm delay, pump malfunction
Alarm delay malfunc.
P1-Heating: 5 sec
P1-Cooling: 5 sec
P1-Exchan.: 20 sec
Alarm delay, misc.
Alarm delay
Filter mon.: 180 sec
Flow switch: 5 sec
Frost prot.: 0 sec
Ext. Frost prot. DI refers to the digital input signal Deicing Heat exchanger.
Alarm delay, misc. 2
Alarm delay
Deicing DI: 0 sec
Fire alarm: 0 sec
Ext. alarm: 0 sec
Frost protection DI refers to the digital input signal De-icing thermostat exchanger.
Alarm delay, misc. 3
Alarm delay
Elec. heat: 0 sec
Sensor error: 5 sec
Rot.sent.exch: 20 sec
15.6.3 Restore alarm
Service alarm
(filter alarm)
Time counter set to
zero: No
15.7 Save and restore settings
Restore factory
settings: No
Restore user settings:
No
In this menu, it is possible to restore all parameters to their factory settings or to the user settings
they were saved as earlier, see below.
Save user settings: No
The present configuration can be saved in a separate memory area and can later be restored using
the previous menu, "Restore user settings".