59
Options
(See back of the manual for maintenance log)
Heating Coils
One or two row hot water and steam heating
and preheating coils can be factory installed.
All valve controls for heating operation are
field supplied and field installed. Hot water
and steam coil connections are spun copper
tube.
Water coils must not be subjected to entering
air temperatures below 38°F to prevent coil
freeze-up. If air temperature across the coil is
going to be below this value, use a glycol
solution to match the coldest air expected.
Table 14 - Hot Water Coil Connection Sizes
Table 15 - Steam Distributing Coil Connection Sizes
Model (RZA-)
Heating Coil Size
Hot Water Coil
Connection Size
Coil
Quantity*
045, 055, 065, 075
A, B, C, D
2-1/8”
1/1
090, 105, 120, 130, 140
A
2-1/8”
2/2
B, C, D
2-1/8”
1/1
145, 160, 180, 200, 220, 240
A, B
2-1/8”
2/2
C, D
2-1/8”
1/1
* In/Out Connections
Model (RZA-)
Heating Coil Size
Steam Coil
Connection Size
Coil
Quantity*
045, 055, 065, 075
A
2-1/8”
2/2
B, C, D
2-1/8”
1/1
090, 105, 120, 130, 140
A
2-1/8”
4/4
B
2-1/8”
2/2
C, D
2-1/8”
1/1
145, 160, 180, 200, 220, 240
A
2-1/8”
4/4
B,C
2-1/8”
2/2
D
2-1/8”
1/1
* In/Out Connections
Piping shall be in accordance with
national and local codes. Pressure
limiting devices, backflow preventers
and all other safety requirements are
the sole responsibility of the installing
contractor.
WARNING
Installing Contractor is responsible for
proper sealing of the water piping
entries into the unit Failure to seal the
entries may result in damage to the
unit and property.
CAUTION