52
7.
Evacuate the suction filter assembly
to 300 microns
8.
Open both shut-off valves
VFD Controlled Condenser Fan Startup
When selected, the condenser fan VFD’s are
factory provided and factory programmed.
The VFD’s receive input from pressure
transducers on each refrigerant circuit and
vary the fan speed based on the pressure
inputs to maintain a discharge (head)
pressure. Standard pressure setpoint is 340
psi for standard air-cooled systems and 400
psi for modulating hot gas reheat air-cooled
systems.
The AAON Condenser Head Pressure
Module is used to maintain a discharge
pressure. The VFD is factory wired to the
outputs of the AAON Condenser Head
Pressure Module. See AAON literature for
additional information.
(
Low Sound Condenser Fan EC Motor
Startup
AAON Condenser Head Pressure Module is
used for variable speed control of the motor
to maintain a head pressure. The motor must
be factory wired to the PWM outputs of the
AAON Condenser Head Pressure Module.
See AAON literature for further information
(https://www.aaon.com/Controls).
Note
High voltage wires out of the motor:
Black & Brown – 1 Phase Line Voltage
Green - Ground
Low control voltage wires out of the motor:
Blue – Common
Yellow – Variable Speed Control
Table 13 - EC Condenser Fan Cycling Options
Color
T erminal
Customer
Connection
Option 1
Option 2
Option 3
Option 4
Option 5
Black
0.50 BWS
L1
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
Brown
0.50 BWS
L2
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
208-230 VAC
Green
#10
EYELET
Ground
GND
GND
GND
GND
GND
Blue
0.50 BWS
Common
Common
24 VAC
24 VAC
24 VAC
24 VAC
Yellow
0.50 BWS
Signal
PWM
24 VAC
24 VAC
White
0.50 BWS
Signal
24 VAC
24 VAC
Orange
0.50 BWS
Signal
24 VAC
24 VAC
RPM
300-1100
300
500
850
1100
Rotation
CCW
CCW
CCW
CCW
CCW
ECM T oolbox ID
Variable
Speed 4
Speed 3
Speed 2
Speed 1
20% PWM RPM
300
100% PWM RPM
1100