31
Pluggable Screw Terminal Block H5
24V
= 24VAC power output for thermostat.
NS_OV
= Night setback override input.
Input requires 24VAC to activate.
O
= Thermostat input for reversing valve
operation. Input requires 24VAC to
activate.
COM
= 24VAC common for thermostat
power.
G
= Thermostat input for fan operation.
Input requires 24VAC to activate.
NS_TH
= Night setback compressor enable.
Input requires 24VAC to activate.
Y
= Thermostat input for compressor
operation. Input requires 24VAC to
activate.
AL
= 24VAC wet alarm output.
Pluggable Screw Terminal Block H1
+
= Network terminal used for
communication with the expansion board.
-
= Network terminal used for
communication with the expansion board.
S
= Shield
Quick Disconnect Terminals
P1 - AUX
= Auxiliary alarm terminal. Dry
contact with AUX IN enables alarm.
P2 - AUX IN
= Auxiliary alarm terminal.
Dry contact with AUX enables alarm.
P3
- TEST
= Delay override terminal. Dry
contact with TEST IN enables the delay
override function.
P4 - TEST IN
= Delay override terminal.
Dry contact with TEST enables the delay
override function.
Wiring Harness H3
PURPLE
= Evaporator coil temperature
sensor. To be used with 10k Type III
thermistors.
WHITE
= Evaporator coil temperature
sensor. To be used with 10k Type III
thermistors.
TAN
= Water output temperature sensor.
To be used with 10k Type III thermistors.
GRAY
= Water output temperature sensor.
To be used with 10k Type III thermistors.
PINK
= Not used
BROWN
= Condensate drain pan sensor
input.
GREEN
= Low pressure switch. Input
requires a normally closed switch.
ORANGE
= Low pressure switch. Input
requires a normally closed switch.
BLACK
= High pressure switch. Input
requires a normally closed switch.
YELLOW
= High pressure switch. Input
requires a normally closed switch.
RED
= 24VAC power.
BLUE
= 24VAC common.
Wiring Harness H6
BLACK
= Reversing valve 24VAC output.
RED
= Reversing valve common wire.
BLUE
= Fan 24VAC output.
BROWN
= Fan common wire.
GREEN
= Compressor contactor 24VAC
output.
WHITE
= Compressor contactor common
wire.
Alarm Status LED D5
See Table 8 for flash codes.
Relay Status LEDs
COMP = Compressor Relay
ALARM = Alarm Relay
FAN = Fan Relay
RV = Reversing Valve Relay
Dip Switch SW1
See Table 9 - Glycol Percentage Setpoints