22
manual flow valves must be of the ball valve
design. Globe or gate valves must not be used
due to high pressure drops and poor throttling
characteristics.
Pressure and temperature ports are
recommended in water supply and return
lines for system balancing. Locate these
openings 5 to 10 pipe diameters from the unit
water connections. To allow for mixing and
temperature stabilization, wells in the water
piping must extend at least ½ pipe diameter
into the pipe.
Piping systems must not exceed 10 ft/sec
fluid velocity to ensure tube wall integrity
and reduce noise.
Electrical
Verify the unit nameplate agrees with power
supply. WSHP Series units are provided with
single point power wiring connections. A
complete set of unit specific wiring diagrams,
showing factory and field wiring are located
inside the controls compartment panel.
Table 4 - Nameplate Voltage Markings & Tolerances
Hz Nameplate
Voltage
Nominal
System
Voltage
Operating Voltage
Range
1
Acceptable
Performance Range
2
Min
Max
Min
Max
60
115
120
104
127
108
126
208/230
208/240
187
254
187
252
208
208
187
228
187
228
230
240
208
254
216
252
265
277
240
293
249
291
460
480
416
508
432
504
575
600
520
635
540
630
Notes:
1.
Operating voltage is the min and max voltage for which the unit can function. Never
operate outside of this min and max voltage.
2.
The Acceptable Performance Range is the min and max voltage for which the unit
performance is designed and rated to give acceptable performance
3.
Note:
All units are factory wired for either 115V, 208V/230V, 265V, 460V, or 575V.
The transformer configuration must be
checked by a qualified technician prior to
service, especially if unit is to be connected
to a 208V or 230V supply. Note: All our
units are default wired to 208V for the
208V/230V option. To utilize 230V service,
interchange the yellow and red wire terminals
from the transformer.
Red-Black for 208V
Yellow-Black for 230V
Disconnect all electrical power
sources before servicing the unit.
More than one power source may be
provided. Failure to do so may result
in injury or death from electrical shock
or entanglement in moving parts.
WARNING