MHGRV-X Field Technical Guide

INPUTS AND OUTPUTS

Inputs and Outputs

I/O Map

The following inputs and outputs are available on the MHGRV-X. 

See 

Table 2, this page

 to reference the Input/Output Map.

NOTE:  

All analog and 24 VAC contact closure inputs are 

used only in Stand-Alone operation.

Analog Inputs

SAT: Supply Air Temperature Sensor

Used in Stand-Alone operation and when MODGAS is connected 

to a CAV/VAV or MUA controller. The Supply Air Temperature 

Sensor is the main control input. This sensor has to be installed 

for the unit to operate. The Supply Air Temperature Sensor is 

located in the discharge air stream and monitors the HVAC unit’s 

Supply Air Temperature to maintain the Supply Air Temperature 

Setpoint.

RST IN: Reset Signal

Used only in Stand-Alone operation. The Discharge Temperature 

Setpoint can be reset by supplying a 0-10 VDC signal to the 

RESET IN low voltage terminal block. This reset signal is 

optional and need only be used if you require resetting of the 

discharge air temperature.

AUX IN: Auxiliary Reheat Valve Input

Used when AUX mode is configured as enabled. This input looks 

at a 0-10 VDC signal to control the valve position. 

•  0VDC = 0% Reheat Valve position
•  5VDC = 50% Reheat Valve position
•  10VDC = 100% Reheat Valve position.

Binary Inputs

REHEAT EN: Reheat Enable Contact

Used only in Stand-Alone operation. When a call for 

dehumidification is initiated by another controller, this 

interlocked 24 VAC wet contact closure is used to enable the 

MHGRV-X.

HEAT OVR: Heating Override

Used only in Stand-Alone operation. When a call for heating is 

initiated by the HVAC unit, this interlocked 24 VAC wet contact 

closure is used to override the MHGRV-X Dehumidification 

Mode.

COOL OVR: Cooling Override

Used only in Stand-Alone operation. When a call for cooling is 

initiated by the HVAC unit, this interlocked 24 VAC wet contact 

closure is used to override the MHGRV-X Dehumidification 

Mode.

Relay Outputs

FAN: Fan Enable

When a call for Dehumidification, Cooling Override, or Heating 

Override is received, this relay will be closed to energize the 

HVAC unit Supply Fan.

CMP: Compressor Enable

When a call for Dehumidification or Cooling Override is 

received, this relay will be closed to energize the Compressor(s).

VALVE: Flush Active Signal / Compressor 2

If configured as Flush, this relay will be active any time a Flush 

Cycle is active. When the Flush Cycle ends this relay will turn 

off until the next flush occurs.  
If configured as Compressor 2, this relay will be used to control 

a second Compressor when there is a call for Dehumidification. 

Compressor 2 will come on 30 seconds after the first Compressor 

activates. Compressor 2 has a minimum run time of 10 minutes, 

and will turn off if the Reheat Valve is at 100% and the Supply 

Air Temperature is 5°F below setpoint for one minute. After 

being off for 10 minutes, it can come back on if the Supply Air 

Temperature is 5°F above setpoint and the valve is at 0%.

Table 2:  MHGRV-X Inputs and Outputs 

ANALOG INPUTS

1

Supply Temperature

2

Reset Signal

3

AUX Input

BINARY INPUTS

1

Reheat Enable

2

Heating Override

3

Cooling Override

RELAYS

1

Fan

2

Compressor

3

Flush Active Signal / Compressor 2

4

Auxiliary / Reversing Valve

Содержание MHGRV-X

Страница 1: ...MHGRV X Controller Field Technical Guide...

Страница 2: ...21 AAON Inc All rights reserved throughout the world AAON is a registered trademark of AAON Inc Tulsa OK AAON assumes no responsibility for errors or omissions in this document This document is subjec...

Страница 3: ...s Map and Main MHG REHEAT Screens 13 Status and Alarm Screens 14 Setpoint and Force Valves Screens 15 TROUBLESHOOTING 16 LED Diagnostics 16 Alarms 17 Other Checks 18 APPENDIX A SAT SENSOR 20 Supply Ai...

Страница 4: ...21 Table 9 Stand Alone Mode SAT OPTIONS Jumper Settings 21 Table 10 Communications Mode SAT OPTIONS Jumper Settings 21 Table 11 Reheat Expansion Module ALARM LED Blink Codes 27 FIGURES Figure 1 MHGRV...

Страница 5: ...sing the MHGRV X to replace an existing MHGRV II Controller see Appendix B page 22 for details See Figure 1 this page for dimensions Features The MHGRV X provides the following Can be operated as a st...

Страница 6: ...ire size for all sensors should be 24 gauge Some sensors require two conductor wire and some require 3 or 4 conductor wire 5 Minimum wire size for 24 VAC thermostat wiring should be 22 gauge 6 Be sure...

Страница 7: ...rature Sensor is attached to the AAON unit controller See Figure 2 this page See the SATWiring Conditions Table and SAT OPTIONS jumper settings in Tables 8 and 10 page 21 Figure 2 MHGRV X to AAON Unit...

Страница 8: ...Transformer Minimum Mount In Supply Air Duct RED GRN WHT BLK Condenser Valve 1 HGR Valve 1 RED GRN WHT BLK COMM See SAT OPTIONS table for Jumper Settings Only one Supply Air Temperature Sensor can be...

Страница 9: ...g Override Used only in Stand Alone operation When a call for heating is initiated by the HVAC unit this interlocked 24 VAC wet contact closure is used to override the MHGRV X Dehumidification Mode CO...

Страница 10: ...can be used in two different modes of operation These modes behave in a similar manner the main difference is the way they receive information to control the dehumidification process The following is...

Страница 11: ...terminate Dehumidification or a Cooling or Heating Override request is made by the HVAC unit controller Any setpoints or signals at the inputs to the MHGRV X will be ignored Auxiliary Mode Communicat...

Страница 12: ...tions Figure 4 LCD Display and Navigation Keys Table 3 Navigation Key Functions NAVIGATION KEY KEY FUNCTION MENU Use the MENU key to move through screens within Main Menu categories and return to the...

Страница 13: ...ress to go to FORCE VALVE Screens FORCE VALVES Press to scroll through FORCE VALVES Screens Main MHG REHEAT Screens Refer to the following map when navigating through the Main Screens From the MHG REH...

Страница 14: ...Valve between 0 100 FORCE The unit is in the Force Mode VLV POS 100 VALVE POSITION 0 to 100 percent SA TEMP XX X SUPPLY AIR TEMPERATURE 40 F to 150 F or 5 C to 65 C If no sensor is detected screen wil...

Страница 15: ...LY AIR SETPOINT This is maximum temperature at which the Supply Air Temperature will reset to Will display only in Stand Alone Mode The Reset SAT Setpoint is set by the LCD Display in Stand Alone Mode...

Страница 16: ...Normally Open Contact is closed VALVE This green LED will light up to indicate that the relay for the VALVE output is energized and its Normally Open Contact is closed AUX This green LED will light up...

Страница 17: ...pen or failed wiring Refer to chart in back of this guide for readings Verify the SAT OPTIONS jumper settings on the MHGRV X for the Supply Air Temperature Sensor Communications Loss Check COMM LED on...

Страница 18: ...the resistance set the meter to Ohms Unplug the sensor connector from the board and measure the resistance across the disconnected wires This resistance should match the corresponding temperature from...

Страница 19: ...2 607 76 24 4 10158 2 577 78 25 6 9711 2 520 80 26 7 9302 2 465 82 27 8 8893 2 407 84 28 9 8514 2 352 86 30 8153 2 297 88 31 1 7805 2 242 90 32 2 7472 2 187 95 35 6716 2 055 100 37 8 6047 1 927 105 4...

Страница 20: ...nt Stand Alone Mode In Stand Alone Mode the SAT Sensor is connected to the MHGRV X If in Stand Alone Mode the MHGRV X is used in conjunction with a Stand Alone MODGAS X the SAT sensor is shared betwee...

Страница 21: ...ble Install Supply Air Sensor in AAON unit controller Connect to AAON unit controller using I2 C cable VCM VAV CAV MUA MUA II MUA IID Install Supply Air Sensor in MODGAS X Connect to AAON unit control...

Страница 22: ...tep 1 Disconnect power from the MHGRV II Step 2 The Supply Air Temperature Sensor needs to remain installed on whatever controller it is currently on If it is currently installed on the MHGRV II then...

Страница 23: ...multiple sets of valves See Figure 8 this page for dimensions Features The Reheat Expansion Module provides the following Up to seven Reheat Expansion Modules can be used Each Reheat Expansion Module...

Страница 24: ...ller or Module is not operating correctly General Wiring Information For the wiring diagram to use when the MHGRV X is connected to anAAON unit controller see Figure 2 page 7 For the Stand Alone wirin...

Страница 25: ...connectors Up to seven Reheat Expansion Modules can be used Apply power to the first Reheat Expansion Module in a series The last Reheat Expansion Module in a series connects to the MHGRV X using an E...

Страница 26: ...il return to the compressor the Hot Gas Reheat Coil will be flushed of liquid refrigerant by moving the Modulating Gas Reheat Valve to its maximum position for a short interval Cooling Flush If the un...

Страница 27: ...every second The COMM LED should blink simultaneously on all modules Binary Input LED COMPRESSOR ENABLE This green LED will light up when the Reheat is enabled LED Troubleshooting POWER LED When the R...

Страница 28: ...he STATUS LED will blink six times A The valve position displayed on the MHGRV X Status Screen should match the expansion module s valve position The expansion module must have the enable signal activ...

Страница 29: ...press the ENTER key once from the main screen It should display S A MODE LOCKED 3 The MHGRV X must be configured for EXP VLVS ENABLED in the MHGRV X Configuration Screens If this is true the COMM LED...

Страница 30: ...rved AAON Factory Technical Support 918 382 6450 techsupport aaon com AAON Controls Support 866 918 1100 Monday through Friday 7 00 AM to 5 00 PM Central Standard Time Controls Support website www aao...

Отзывы: