MHGRV-X Field Technical Guide
TROUBLESHOOTING
Other Checks
Supply Air Temperature Sensor
If you suspect the Supply Air Temperature Sensor is not reading
correctly, make sure the wiring terminal connections are tight and
that any wiring splices are properly connected. You can check the
operation of the Supply Air Temperature Sensor by measuring
the resistance or voltage using a digital multimeter.
Measuring Voltage
Set the meter to DC Volts. Place the positive probe on the AIN
terminal and the negative probe on the GND terminal. Read the
DC Volts and find that voltage in
Table 6, this page
and
Table 7,
page 19
. Read the temperature corresponding with that voltage
and determine if this is close to the actual temperature the sensor
is exposed to. If the temperature from the chart is different by
more than a few degrees, you probably have a defective or
damaged sensor.
Thermistor Sensor Testing
Instructions
1. Use the resistance column to check the thermistor
sensor while disconnected from the controllers (not
powered).
2. Use the voltage column to check sensors while
connected to powered controllers. Read voltage with
meter set on DC volts. Place the “-” (minus) lead on
GND terminal and the “+” (plus) lead on the sensor
input terminal being investigated.
Measuring Resistance
To read the resistance, set the meter to Ohms. Unplug the
sensor connector from the board and measure the resistance
across the disconnected wires. This resistance should match the
corresponding temperature from
Table 6, this page
and
Table
7, page 19
.
Temp
(°F)
Temp
(°C)
Resistance
(Ohms)
Voltage @
Input (VDC)
-10
-23.3
93333
2.98
-5
-20.6
80531
2.94
0
-17.8
69822
2.89
5
-15
60552
2.83
10
-12.2
52500
2.77
15
-9.4
45902
2.71
20
-6.6
40147
2.64
25
-3.9
35165
2.57
30
-1.1
30805
2.49
35
1.7
27140
2.41
40
4.4
23874
2.33
45
7.2
21094
2.24
50
10
18655
2.15
52
11.1
17799
2.11
54
12.2
16956
2.08
56
13.3
16164
2.04
58
14.4
15385
2.00
60
15.6
14681
1.96
62
16.7
14014
1.93
64
17.8
13382
1.89
66
18.9
12758
1.85
68
20
12191
1.81
69
20.6
11906
1.79
70
21.1
11652
1.78
71
21.7
11379
1.76
Temp
(°F)
Temp
(°C)
Resistance
(Ohms)
Voltage @
Input (VDC)
72
22.2
11136
1.74
73
22.8
10878
1.72
74
23.3
10625
1.70
75
23.9
10398
1.68
76
24.4
10158
1.66
78
25.6
9711
1.63
80
26.7
9302
1.59
82
27.8
8893
1.55
84
28.9
8514
1.52
86
30
8153
1.48
88
31.1
7805
1.45
90
32.2
7472
1.41
95
35
6716
1.33
100
37.8
6047
1.24
105
40.6
5453
1.16
110
43.3
4923
1.09
115
46.1
4449
1.02
120
48.9
4030
.95
125
51.7
3656
.88
130
54.4
3317
.82
135
57.2
3015
.76
140
60
2743
.71
145
62.7
2502
.66
150
65.6
2288
.61
TEMPERATURE TO RESISTANCE/VOLTAGE CHART
Table 6: 0-3V Temperature Sensor - Voltage and Resistance for Type III Sensors
Note:
If the voltage is above 3.3 VDC the sensor or wiring is “open.” If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.