![AAON MHGRV-X Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/aaon/mhgrv-x/mhgrv-x_field-technical-manual_3228663019.webp)
19
MHGRV-X Field Technical Guide
TROUBLESHOOTING
Other Checks
Thermistor Sensor Testing
Instructions
1. Use the resistance column to check the thermistor
sensor while disconnected from the controllers (not
powered).
2. Use the voltage column to check sensors while
connected to powered controllers. Read voltage with
meter set on DC volts. Place the “-” (minus) lead on
GND terminal and the “+” (plus) lead on the sensor
input terminal being investigated.
Measuring Resistance
To read the resistance, set the meter to Ohms. Unplug the
sensor connector from the board and measure the resistance
across the disconnected wires. This resistance should match the
corresponding temperature from
Table 6, this page
and
Table
7, page 19
.
Table 7: 0-5V Temperature Sensor - Voltage and Resistance for Type III Sensors
Temp
(°F)
Temp
(°C)
Resistance
(Ohms)
Voltage @
Input (VDC)
72
22.2
11136
2.695
73
22.8
10878
2.665
74
23.3
10625
2.635
75
23.9
10398
2.607
76
24.4
10158
2.577
78
25.6
9711
2.520
80
26.7
9302
2.465
82
27.8
8893
2.407
84
28.9
8514
2.352
86
30
8153
2.297
88
31.1
7805
2.242
90
32.2
7472
2.187
95
35
6716
2.055
100
37.8
6047
1.927
105
40.6
5453
1.805
110
43.3
4923
1.687
115
46.1
4449
1.575
120
48.9
4030
1.469
125
51.7
3656
1.369
130
54.4
3317
1.274
135
57.2
3015
1.185
140
60
2743
1.101
145
62.7
2502
1.024
150
65.6
2288
0.952
Temp
(°F)
Temp
(°C)
Resistance
(Ohms)
Voltage @
Input (VDC)
-10
-23.3
93333
4.620
-5
-20.6
80531
4.550
0
-17.8
69822
4.474
5
-15
60552
4.390
10
-12.2
52500
4.297
15
-9.4
45902
4.200
20
-6.6
40147
4.095
25
-3.9
35165
3.982
30
-1.1
30805
3.862
35
1.7
27140
3.737
40
4.4
23874
3.605
45
7.2
21094
3.470
50
10
18655
3.330
52
11.1
17799
3.275
54
12.2
16956
3.217
56
13.3
16164
3.160
58
14.4
15385
3.100
60
15.6
14681
3.042
62
16.7
14014
2.985
64
17.8
13382
2.927
66
18.9
12758
2.867
68
20
12191
2.810
69
20.6
11906
2.780
70
21.1
11652
2.752
71
21.7
11379
2.722
TEMPERATURE TO RESISTANCE/VOLTAGE CHART
Note:
If the voltage is above 5.08 VDC the sensor or wiring is “open.” If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Содержание MHGRV-X
Страница 1: ...MHGRV X Controller Field Technical Guide...