MHGRV-X Field Technical Guide
WIRING
MHGRV-X to AAON Unit Controller Wiring
Communications Wiring
For connection to a VCCX2 or VCB-X Controller, VCCX2 or
VCB-X Expansion Module, and Reheat Expansion Module, use
an E-BUS Cable to connect to the appropriate E-BUS port on
those modules and/or controller.
For all other controllers, including the VAV/CAV, MUA,VCM,
VCM-X, SA, and RNE Controllers, use an I
2
C Cable connecting
to the appropriate I
2
C ports on those controllers.
When connected to an AAON unit controller, the Supply Air
Temperature Sensor is attached to the AAON unit controller.
See
Figure 2, this page
.
See the SAT Wiring Conditions Table and SAT OPTIONS jumper
settings in
Tables
8 and 10, page 21
.
Figure 2: MHGRV-X to AAON Unit Controller Wiring
Line
Voltage
GND
18-30 VAC
40 VA
Transformer
Minimum
Supply
Air Temperature
Sensor
Mount In Supply
Air Duct
RED
GRN
WHT
BLK
Condenser Valve #1
HGR Valve #1
RED
GRN
WHT
BLK
Supply Air Temperature
Sensor Connects to AI3 & GND
On VCCX2 Controller
MHGRV-X CONTROLLER
Set Jumper To
NORMAL.
Fan
Compressor
Flush Active Signal
2 Position HGR Valve (Optional)
C1
C2
COMM
EBC E-BUS cable
connects to VCCX2
Expansion port
EBC
E-BUS
cable
connects
to Reheat
Expansion
Module
Alternate Configuration
3 Way Valve
RED
GRN
WHT
BLK