19
Heating:
The fan speed for the heating cycle is
selected by adjusting the HEAT tap (see
FIGURE 2) according to TABLE 6.
Table 6 - Heating Fan Speed Tap Settings
F1-060/
F1-036/
HEAT Tap
F1-048
F1-024
(cfm)
(cfm)
1800
1000
A
1400
800
B
1200
600
C
1800
1000
D
ECM Fan Notes
1.
Fan only = 50% of max speed
2.
Dehumidifying speeds
i)
First stage dehumidification =
67% of max speed
ii)
Second stage dehumidification =
45% of max speed
3.
Green Light will blink once per every
100 CFM
4.
Dehumidification terminal is BK. There
must be a constant voltage to this
terminal, and when the voltage is
dropped then dehumidification mode
will begin.
Fan wiring notes:
1.
If only one stage of cooling is used then
jumper Y1 and Y2.
2.
If unit is not heat pump capable then
jumper O and Y1.
3.
If no humidistat is used then jumper BK
and R.
4.
When only one stage of heat is used
jumper W1 and W2.
Reheat Coil Refrigerant Piping
The reheat coil is shipped already
installed on the leaving air section of the
air handling unit. A liquid receiver is
shipped loose with the unit for field
installation.
(See matching condensing unit
installation, operation, & maintenance
manual to determine acceptable refrigerant
line size.)
1.
Run a hot gas line from the outdoor unit
and connect it to the inlet of the stub-out
on the reheat coil.
a.
For vertical (up-flow) units.
The
inlet connection is the left stub-out
when facing the front of the unit.
Connect the hot gas line from the
outdoor unit to the left stub-out.
Connect the check valve (shipped
loose) to the right stub-out in a
direction so that the refrigerant flow
is leaving the right side of the coil.
Be sure to not block access for
service of the air handling unit with
the placement of the check valve.
b.
For horizontal discharge units.
Connect the hot gas line from the
outdoor unit to the upper stub-out
connection of the reheat coil.
Connect the check valve (shipped
loose) to the lower stub-out in a
direction so that the refrigerant is
leaving the bottom side of the reheat
coil. Be sure to not block access for
Содержание F1-060
Страница 31: ...31 ...
Страница 33: ...33 Figure 5 Modulating Hot Gas Reheat Piping Diagram with Air Handling Unit below Condensing Unit ...
Страница 36: ...36 Figure 8 Heat Pump Piping Diagram with Indoor Unit above Outdoor Unit ...
Страница 37: ...37 Figure 9 Heat Pump Piping Diagram with Outdoor Unit above Indoor Unit ...
Страница 38: ...38 Figure 10 Heat Pump Piping Diagram with Modulating Hot Gas Reheat and Indoor Unit above Outdoor Unit ...
Страница 39: ...39 Figure 11 Heat Pump Piping with Modulating Hot Gas Reheat and Outdoor Unit above Indoor Unit ...
Страница 40: ...40 Thermostat Installation and Wiring Figure 12 2 Stage Cooling with Electric Heat ...
Страница 41: ...41 Figure 13 2 Stage Cooling with Heat Pump and Electric Heat ...
Страница 42: ...42 Figure 14 2 Stage Cooling and Electric Heat with Hot Gas Reheat and Humidistat ...
Страница 43: ...43 Figure 15 Main Control Board for Units Equipped with Modulating Hot Gas Reheat ...
Страница 45: ...45 Figure 17 5kW Electric Heat ...
Страница 46: ...46 Figure 18 10 kW Electric Heat ...
Страница 47: ...47 Figure 19 15 kW Electric Heat ...
Страница 48: ...48 Figure 20 20 kW Electric Heat ...
Страница 49: ...49 Figure 21 25 kW Electric Heat ...
Страница 55: ...55 ...