9.4. Cyclic data layout
Once the Industrial Ethernet connection is established between the AD-4411 and PLC, cyclic data exchanges
are performed periodically. The cyclic data consists of the Write data area for sending data from the PLC to the
AD-4411 and the Read data for sending data from AD-4411 to the PLC.
The contents of cyclic data transfer are common to EtherNet/IP, PROFINET, and EtherCAT.
9.4.1. Data layout
Write data (PLC -> AD-4411)
Word No. Data area name Data type Description
Word 0-1 Command value Int32
This area is used to send various commands to AD-4411.
Word 2
Command
UInt16
Read data (AD-4411 -> PLC)
Word No. Data area name Data type Description
Word 0-1 Response value Int32
This area is used to receive the response for a command from
AD-4411.
Word 2
Response
UInt16
Word 3-4 Net value
Int32
Net value
Word 5-6 Gross value
Int32
Gross value
Word 7-8 Status
UInt32
Bits.0-10
-
Bit.11
Hi
Bit.12
OK
Bit.13
Lo
Bit.14
-
Bit.15
Stability
Bit.16
Net value display
Bits.17-18
-
Bit.19
Overload
Bit.20
Zero-setting failed
Bit.21
Tare failed
Bits.22-31
-
The status bit is "1" while the condition is met.