10. TABLE OF TECHNICAL DATA ERP
10.1 TABLE OF TECHNICAL DATA ERP - MEC MIX C 20/35 - 20/90 AXIALS
Positive influence on hS, on (only one possible multiple selection the final result is the sum)
1,0
% F(3)
Room temperature control with presence detection (1%)
No
%
F(3)
Room temperature control with open window control (1%)
No
0,0
%
With remote control option (1%)
Yes
1,0
%
1,9
kW
F(4)
el
max
(consumption of electricity at nominal heat output)
0,409 kW F(4)
el
min
(consumption of electricity at minimum heat output)
0,211 kW F(4)
in case there is not a minimum: elmin = elmax
elsb
(electric consumption in standby mode)
0,009 kW F(4)
P
nom
(rated thermal power of the appliance)
37,77 kW F(4)
Influence of a permanent pilot burner)
0,0
%
F(5)
Pilot burner consumption
0,00
KW
F(5)
NOx emission based on gross caloric value (<130mg / kW)
31
mg/KWh
η
s = 92,5 %
Energy efficiency class
A
η
s=
η
s,on -10% + F(1) + F(2) + F(3) - F(4) - F(%)
Type of device:
Heaters of gaseous fuel
closed
front.
Efficiency of the appliance under nominal conditions (Pci net value)
96,4
%
ηs
,on=
ηth
,non
Not applicable for gas appliances
0,0
%
F(1)
Positive influence on hS, on (only one possibility)
7,0
%
F(2)
two or more phases single phase thermal power without ambient temperature control
0.0%
with manual steps without room temperature control
1.0%
with room temperature control via mechanical thermostat
2.0%
with electronic control of the ambient temperature
4.0%
with electronic control of the room temperature and daily timer
6.0%
with electronic control of the room temperature and weekly timer
7.0%
η
s=
η
s,on -10% + F(1) + F(2) + F(3) - F(4) - F(%)