TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
13
03/18/21
www.atcontrols.com
IOM08139 REVISION 01
FEEDBACK CONFIG submenu
F E E D B A C K
T Y P E :
x x x x
Feedback
Signal Type
Sets type of feedback signal.
10V:
0.0 to 10.8 VDC
mA:
0.0 to 21.5 mA
ON-OFF:
n/A
C A L I B R A T E
Z E R O
x x x x
Calibrate
Feedback Zero
Sets feedback signal zero raw count value. Value is scaled between 12 bit count of 0 and 4095 for the selected
command type range. When selected, use [UP] or [DOWN] to adjust feedback until desired value is measured.
C A L I B R A T E
S P A N
x x x x
Calibrate
Feedback Span
Sets feedback signal span raw count value. Value is scaled between 12 bit count of 0 and 4095 for the selected
command type range. When selected, use [UP] or [DOWN] to adjust feedback until desired value is measured.
POSITION CONFIG submenu
P O S I T I O N
T Y P E :
x x x x
Position Type
Sets type of feedback for positioning.
Limit SW:
Uses limit switch feedback for 2 position on/off control.
Potent:
Uses potentiometer feedback for modulating and proportional positioning control.
C A L I B R A T E
C L O S E P O S
x x x x
Calibrate Close
Position
Only used with potentiometer feedback to set close position. This position will correspond to a 0% input value.
Value is scaled between 12 bit count of 0 and 4095 based on potentiometer reading. When selected, use [UP] or
[DOWN] to drive motor to desired close position.
C A L I B R A T E
O P E N P O S
x x x x
Calibrate Open
Position
Only used with potentiometer feedback to set open position. This position will correspond to a 100% input value.
Value is scaled between 12 bit count of 0 and 4095 based on potentiometer reading. When selected, use [UP] or
[DOWN] to drive motor to desired open position.
T R A V E L
T I M E O U T
x x S
Travel Timeout
Only used with communication bus options. Value should be greater than the normal actuator travel time. The
TMC-4 begins a counter when the motor outputs are energized to control the actuator to the commanded position.
If the counter exceeds the set value it can indicate a jam or obstruction. The actuator may also be travelling slower
due to loading conditions. When selected, use [UP] or [DOWN] to adjust value. Can also be configured via
communication protocol.
60 sec