TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
7
03/18/21
www.atcontrols.com
IOM08139 REVISION 01
TMC-4A002-002
(P1)
Motor / Supply
Terminals
Function
1
Heater L/+
Fused output for heater.
2
Heater N/-
Neutral output for heater, connected to supply N.
3
Supply L/+
Supply Power.
4
Supply N/-
Supply Power.
5
External
Brake
Output that switches supply power when motor outputs are energized. Used for spring return electric actuator
brakes.
AC Operation: Switch off when motor on.
DC Operation: Switch on when motor on.
6
Motor CW
AC: Energize clockwise motor winding.
DC: Switch (+) supply voltage for clockwise operation.
7
Motor CCW
AC: Energize counterclockwise motor winding.
DC: Switch (+) supply voltage for counterclockwise operation.
8
Motor N
AC: Motor neutral, connected to supply N.
DC: not used.
(P2)
Signal / Comm
Terminals
Function
1
+24V Out
Auxiliary 24VDC output.
2
I/O 1
Signal In
Command signal input.
3
Signal GND Command signal reference.
4
I/O 2
Signal Out
Feedback signal output.
5
Signal GND Feedback signal reference.
6
COM2 P
Communication non-inverting input (Channel 2).
7
COM2 N
Communication inverting input (Channel 2).
8
COM1 P
Communication non-inverting input (Channel 1).
9
COM1 N
Communication inverting input (Channel 1).
10
GND
Ground.