WE/XE/SE/XC Series 

Quarter-Turn Electric Actuator 

Installation & Maintenance Manual  

 

 

 

12/17/19 

www.atcontrols.com 

IOM8011 REVISION 01 

  

1.  Purpose 

 

This manual provides explanation on the installation, 
operation and maintenance of WE, SE, XE and XC 
series electric actuators. Not all options are covered in 
this manual. For additional details on an option, refer to 
that option’s specific manual. 

 

 
 

2.  Safety 

 

  Safety Notices 

 

 

WARNING:

 Identifies a potentially 

hazardous situation or practice that may 
lead to personal injury or death. 
 

 

SHOCK HAZARD:

 Indicates dangerous 

voltage may be present. 
 
 

 

CAUTION:

 Indicates general precaution 

that could lead to personal injury or 
damage to equipment. 

 
 

  Safety Instructions 

 

  This device was shipped from the factory in a proper 

condition to be safely installed and operated in a 
hazard-free manner. The notes and warnings in this 
document and on the actuator should be maintained 
and followed to ensure safe operation of the device. 
 

  Take all necessary precautions to prevent damage 

to the actuator due to rough handling, impact, or 
improper storage. 
 

  Do not use abrasive compounds to clean the 

actuator, or scrape metal surfaces with any objects. 
 

  The system controlling the actuator must have 

proper safeguards to prevent damage to equipment, 
or injury to personnel should failure of system 
components occur. 
 

  A qualified person in terms of this document is one 

who is familiar with the installation, commissioning 
and operation of the electric actuator and who has 
appropriate qualifications, which may include: 

 
 
 

o

  Is trained in the operation and maintenance of 

electric equipment and system in accordance 
with established safety practices. 

o

  Is trained or authorized to energize, de-energize, 

ground, tag and lock electric circuits and 
equipment in accordance with established safety 
practices. 

o

  In cases where the actuator is installed in a 

potentially explosive (hazardous) location, is 
trained in the installation, commissioning, 
operation and maintenance of equipment in 
hazardous locations. 

 

  The actuator must be installed, commissioned, 

operated and repaired by qualified personnel. 
 

  All installation, commissioning, operation and 

maintenance must be performed under strict 
observation of all applicable codes, standards and 
safety regulations. 
 

  Reference is specifically made here to observe all 

applicable safety regulations for actuators installed 
in potentially explosive (hazardous) locations. 

 
XC actuators must observe the following installation 
instructions. 

  Use supply wires suitable for at least 90°C (194°F) 

  Disconnect circuit before removing cover. 

  Install in location that shall not be exposed to acetic 

acid or methanol. 

  Install a seal within 50mm of the enclosure. 

 
 

3.  Introduction 

 

  Storage 

 
Actuators must be installed in a clean, cool and dry 
environment off the floor and covered.  
 
Actuators should be stored with the cover installed and 
cable entries sealed.  
 
When actuators are stored outdoors, they must be 
stored off the ground and high enough to prevent being 
immersed in water or buried in snow. 
 
 
 
 

Содержание Triad Controls SE Series

Страница 1: ...XC Series Quarter Turn Electric Actuator Installation Maintenance Manual 1 12 17 19 www atcontrols com IOM8011 REVISION 01 Installation and Operation Manual WE XE SE 690 thru WE XE SE 25900 XC 00690 thru XC 25900 ...

Страница 2: ...nal Features 5 Standard Model External Parts 6 4 4 1 Size 690 thru 10500 6 4 4 2 Size 17500 and 25900 6 4 4 3 Standard Model Internal Parts 6 Manual Operation Handwheel 7 Space Heater 7 5 Installation 7 Pre Installation 7 Tools 7 Actuator Mounting 8 5 3 1 Mounting Base Details ISO 5211 8 5 3 2 Drive Bushing 9 Housing Cover 9 Limit Switch Setting 9 Torque Switch Setting 10 Mechanical Travel Stop Ad...

Страница 3: ...tallation commissioning and operation of the electric actuator and who has appropriate qualifications which may include o Is trained in the operation and maintenance of electric equipment and system in accordance with established safety practices o Is trained or authorized to energize de energize ground tag and lock electric circuits and equipment in accordance with established safety practices o ...

Страница 4: ...e output shaft Accurate positioning is achieved by the indicator cam shaft connecting directly to the output drive Standard Specification Enclosure WE Weatherproof IP67 CSA approved for NEMA 4 4X SE Submersible IP68 10m for 72hrs Type 4 4X 6 XE ATEX IECEx certified to Ex d IIB T4 Gb IP67 XC CSA Class I Division 1 Group C D T4 Ex d IIB T4 Gb Class I Zone 1 AEx d IIB T4 Gb Supply Power 12 24VDC 24 1...

Страница 5: ...vo cards WE XE SE XC Series Additional Aux switches SPDT 250V AC 10A Rating WE XE SE Series SICU Semi integral control unit Local Remote Selector Switches WE XE SE Series except 690 ICU Intelligent Digital control unit Local Remote Selector Switches WE XE SE Series except 690 Current position transmitter output 4 20mA DC WE XE SE Series Extended Rotation 120º 180º 270º turn WE XE SE Series except ...

Страница 6: ...ts CAUTION The 690 size actuator does not contain torque switch assembly Forcing actuator into mechanical stops or preventing rotation in some other manner may damage motor Window Indicator Lever Hand Wheel Body Cable Entries Mechanical Travel Stop Base Top Cover Window Indicator Lever Hand Wheel Base Cable Entries Mechanical Travel Stop Gear Box Top Cover Limit Switch Assembly Capacitor Motor Ter...

Страница 7: ... Heater Condensation may form in the actuator due to change in ambient temperature Powering the internal space heater will help prevent this Standard heaters are ceramic with thermostat to prevent over heating above 140 F 60 C Actuator Size Voltage Heater 690 110VAC 220VAC 24VDC 12VDC 5W 4 5kΩ 5W 18kΩ 5W 200Ω 5W 47Ω 1350 to 25900 110VAC 220VAC 24VDC 12VDC 10W 2kΩ 10W 8kΩ 10W 100Ω 10W 27Ω 5 Install...

Страница 8: ...t be used To avoid backlash there should be no flexibility in the mounting Valve output shaft must be in line with actuator output drive to avoid side loading the shaft Operate with handwheel before fully tightening mounting hardware to ensure correct alignment Ensure both valve and actuator are in the same open or closed position before mounting CAUTION Prior to mounting the actuator must be chec...

Страница 9: ... Hex Size 690 6mm 1350 1700 8mm 2640 4400 5200 10mm 6900 10500 10mm 17500 25900 10mm Limit Switch Setting WARNING Hazardous voltage Turn off all power and lock out service panel before installing or modifying any electrical wiring Use caution when energizing inputs CAUTION Setting limit switches incorrectly may result in actuator stopping by the mechanical stops This may overheat the motor and for...

Страница 10: ...o set the close mechanical stop bolt operate the actuator clockwise to the Close CW position until the CLS limit switch trips Tighten the close travel stop bolt until it stops on the secondary worm wheel gear then loosen the stop bolt back out by 3 turns Retighten the jam nut To set the open mechanical stop bolt operate the actuator counterclockwise to the Open CCW position until the OLS limit swi...

Страница 11: ... Unused conduit entries must be closed off with plug fitting approved for use per actuator enclosure ratings CAUTION Each actuator must have its own independent control contact Actuators wired in parallel will not operate properly and doing so may cause damage to the actuator Terminals in 690 actuator accept maximum wire size of 16AWG Terminals in 1350 thru 25900 size actuators accept maximum wire...

Страница 12: ...el limit switches 6 3 3 Jamming If the actuator travels into a mechanical travel stop the worm gear will jam Remove power from the command input Briefly apply power in the reverse direction to release the pressure from the worm gear The limit switches and mechanical travel stops should be readjusted per the instructions if jamming occurs 7 Maintenance WARNING o Hazardous voltage Turn off all power...

Страница 13: ... to perform its intended function safely during its useful life However the purchaser or user of A T Controls products should be aware that A T Controls products might be used in numerous applications under a wide variety of industrial service conditions Although A T Controls can provide general guidelines it cannot provide specific data and warnings for all possible applications The purchaser use...

Отзывы: