background image

                                      

 

 

TDC-100 Series 

AC Digital High-Resolution Controller 

Installation & Operation Manual  

 

 

07/24/20 

www.atcontrols.com 

IOM08032 REVISION 01 

 

 
The Triac TDC-100 is a high performance digital 
positioner intended to control AC actuators, providing 450 
points of resolution with quarter turn actuators ranging 
from 2 sec to 120 sec and rated for 25% duty or more.  
The TDC-100 has many automatic advanced features 
that will enhance any actuator while making it easy to 
install and set up. 
 
The simple three button control is used to configure all 
parameters the unit needs for a wide variety of 
applications, and allows the 

open

 and 

closed

 positions to 

be easily set for direct or reversing acting without any 
rewiring.  The unit can be configured for various 
command types (4-20mA, 1-5V, 0-5V, 0-10V, or a digital 
command) and its default operation upon loss of 
command. 

 

Various option modules are easily plugged into the unit, 
providing other features such as a position feedback 
signal (current or voltage), auxiliary switches, fault relay 
contact, or digital communications.  A wide range of data 
is accessible through a digital communications module, 
providing additional control or information.

 

 
 

 

TDC-100

 

 

AC Digital High-Resolution Controller 

 
 

 

 

 

 

FEATURES 

 

 Positions to ±0.1

 with quarter-turn actuators ranging from 2 sec to 120 sec (with or without a brake). 

 

 

Adaptive Control

 feature continuously adjusts for load and actuator conditions and eliminates calibration procedures 

and auto-cal operations. 

 

 Three button control provides easy setup and eliminates the need for instrumentation. 

 

 

Polarity Detection

 feature allows direct or reverse acting operation without re-wiring. 

 

 

Electronic Brake

 feature can eliminate need for a mechanical brake in many applications, and extends mechanical 

brake life when used. 

 

 

Stall Detection

 feature protects actuator motor from a stall condition. 

 

 Automatic 

Duty Cycle Control

 feature prevents shutdown of a process due to a thermal overload of the actuator 

motor, and allows actuators rated for 25% duty or more to be safely used. 

 

 Operating temperature range of 0 to 60

Содержание TRIAC TDC-100 Series

Страница 1: ...ch as a position feedback signal current or voltage auxiliary switches fault relay contact or digital communications A wide range of data is accessible through a digital communications module providin...

Страница 2: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 2 07 24 20 www a tcontrols com IOM08032 REVISION 01 OUTLINE TDC 100 117VAC TDC 100A 234VAC TDC 100B 24VAC...

Страница 3: ...ed as a direct replacement for those units in nearly any application The simple three button control MODE and allows the user to perform a complete set up from the unit itself without the need for any...

Страница 4: ...used auto manual station switches are easily implemented with low voltage low current switches See Special Applications for more details The factory installed jumper between pins 1 and 2 enables norm...

Страница 5: ...of 10V 5V 20mA or 100 will position the actuator to the defined open position When the TDC 100 is configured to use a 0 5V 0 10V 1 5V or 4 20mA command the command signal should be connected to the ap...

Страница 6: ...unction the TDC 100 will begin moving the actuator to the previously set position It is not necessary to make an adjustment if the unit has been previously set to the desired position COMAND TYPE The...

Страница 7: ...ed fault is corrected the unit may display another fault that has not been corrected The following table provides a summary of the Fault indicators which is followed by a description of each fault RED...

Страница 8: ...100 automatically compensates for changes in a mechanical brake s performance due to temperature or age Note that the actuator s limit switches should be set outside of the operating range set by the...

Страница 9: ...ODULES Various option modules can be plugged into the TDC 100 option module connector J3 Option modules provide additional features such as position feedback signals auxiliary switch outputs or digita...

Страница 10: ...and threshold 0 75V 1 5 VDC input 1 5V 2 10 VDC input 3mA 4 20mA input Command Out of Range threshold 5 25V 0 5 VDC 1 5 VDC input 10 5V 0 10 VDC 2 10 VDC input 21mA 4 20mA input FEEDBACK SIGNAL INPUT...

Страница 11: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 11 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Input Signal Configurations...

Страница 12: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 12 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications...

Страница 13: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 13 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications continued...

Страница 14: ...or stable command signal Triac output failure Motor buzzes and overheats Perform appropriate remedy then replace the unit Exposure to water from conduit entrance Exposure to water from unsealed actuat...