TDC-100 Series 

AC Digital High-Resolution Controller 

Installation & Maintenance Manual  

 

 

14 

07/24/20 

www.atcontrols.com 

IOM08032 REVISION 01 

 

TROUBLESHOOTING 

 
 

PROBLEM 

POSSIBLE CAUSES 

REMEDIES 

No response from unit 
(All lights are off) 

No power. 
 
Excessive voltage applied to unit. 
 
Blown or missing fuse. 
 

Check power source. 
 
Replace unit. 
 
Replace with appropriate fuse; see 
“Specifications in manual. 

No response from unit, and no response from 
adjust (▲ and ▼) or MODE buttons. 
(MANUAL/FB POT CAL light is lit solid) 

Jumper wire on J7 terminal block is missing. 
 
Auto/Manual station is improperly wired. 
 

Install jumper wire on J7 terminal block. 
 
Check wiring on Auto/Manual station; see 
“Override Mode” in manual. 

Actuator rotates valve backwards 

Actuator or valve is mounted incorrectly on 
coupling. 
 
Actuator needs to be reverse acting. 
 

Remount actuator as necessary. 
 
 
Refer to “Close” and “Open” modes in manual. 

Actuator does not respond to input signal (all 
FAULT indicators off). 

Closed and open positions are set to the same 
position. 

Set close and open settings; refer to “Close” 
and “Open” modes in manual. 

Motor 1 or 2 No Motion (Stall) FAULT indicators 
flash after actuator reaches fully closed or open 
position. 

Closed or open limit switches set inside the 
operating range. 
 
Torque switches trip due to mechanical end 
stops set inside the operating range. 

Adjust limit switch cams; refer to “Close” and 
“Open” modes in manual. 
 
Adjust mechanical end stops; refer to “Close” 
and “Open” modes in manual. 

AUX CLOSE OUTPUT or AUX OPEN OUTPUT 
indicators flash. 
 
If an OTR-100 or OTR-101 option module is not 
installed, no remedy is required. 

Actuator position is near close or open. 

If and OTR-100 or OTR-101 option module is 
installed, set Aux Close and Aux Open 
positions; refer to “Aux Close Output” and “Aux 
Open Output” modes in manual. 

Actuator hunts for position. 

Sloppy gear tooth engagement. 
 
 
No motor brake or brake slipping. 
 
Unstable command input signal from PID 
control loop. 

Adjust feedback potentiometer gears for tight 
engagement. 
 
Install or repair motor brake. 
 
Adjust PID parameters for stable command 
signal. 

Triac output failure 
(Motor buzzes and overheats). 
 
Perform appropriate remedy, then replace the 
unit. 

Exposure to water from conduit entrance. 
 
Exposure to water from unsealed actuator 
housing. 
 
Exposure to moisture from condensate. 
 
 
Corrosion from exposure to salts or acids. 
 
External power applied to motor connections as 
J1-1 or J1-3. 
 
Motor capacitor is defective or has incorrect 
voltage rating. 
 
Lightning or power surge. 

Install drip loop at conduit entrance. 
 
Inspect and/or replace actuator housing gasket; 
use actuator with proper sealing. 
 
Use heater and thermostat and/or desicant 
packets. 
 
Use corrosion inhibitors and desicant packets. 
 
Remove connector J1 prior to applying external 
power. 
 
Replace motor capacitor. 
 
 
Replace unit. 

 
 

A-T Controls product, when properly selected, is designed to perform its intended function safely during its useful life.  However, the purchaser or user of A-T Controls products 
should be aware that A-T Controls products might be used in numerous applications under a wide variety of industrial service conditions.  Although A-T Controls can provide 
general guidelines, it cannot provide specific data and warnings for all possible applications.  The purchaser / user must therefore assume the ultimate responsibility for the 
proper sizing and selection, installation, operation, and maintenance of A-T Controls products.  The user should read and understand the installation operation maintenance 
(IOM) instructions included with the product and train its employees and contractors in the safe use of A-T Controls products in connection with the specific application.  
 
While  the  information  and  specifications  contained  in  this  literature  are  believed  to  be  accurate,  they  are  supplied  for  informative  purposes  only.  Because  A-T  Controls  is 
continually improving and upgrading its product design, the specifications, dimensions and information contained in this literature are subject to change without notice.  Should 
any question arise concerning these specifications, the purchaser/user should contact A-T Controls.   
 
For product specifications go to 

http://download.a-tcontrols.com/

  

 
A-T Controls, Inc. • 9955 International Boulevard, Cincinnati, OH 45246 • Phone: (513) 530-5175 • Fax: (513) 247-5462 • 

www.atcontrols.com

 

Содержание TRIAC TDC-100 Series

Страница 1: ...ch as a position feedback signal current or voltage auxiliary switches fault relay contact or digital communications A wide range of data is accessible through a digital communications module providin...

Страница 2: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 2 07 24 20 www a tcontrols com IOM08032 REVISION 01 OUTLINE TDC 100 117VAC TDC 100A 234VAC TDC 100B 24VAC...

Страница 3: ...ed as a direct replacement for those units in nearly any application The simple three button control MODE and allows the user to perform a complete set up from the unit itself without the need for any...

Страница 4: ...used auto manual station switches are easily implemented with low voltage low current switches See Special Applications for more details The factory installed jumper between pins 1 and 2 enables norm...

Страница 5: ...of 10V 5V 20mA or 100 will position the actuator to the defined open position When the TDC 100 is configured to use a 0 5V 0 10V 1 5V or 4 20mA command the command signal should be connected to the ap...

Страница 6: ...unction the TDC 100 will begin moving the actuator to the previously set position It is not necessary to make an adjustment if the unit has been previously set to the desired position COMAND TYPE The...

Страница 7: ...ed fault is corrected the unit may display another fault that has not been corrected The following table provides a summary of the Fault indicators which is followed by a description of each fault RED...

Страница 8: ...100 automatically compensates for changes in a mechanical brake s performance due to temperature or age Note that the actuator s limit switches should be set outside of the operating range set by the...

Страница 9: ...ODULES Various option modules can be plugged into the TDC 100 option module connector J3 Option modules provide additional features such as position feedback signals auxiliary switch outputs or digita...

Страница 10: ...and threshold 0 75V 1 5 VDC input 1 5V 2 10 VDC input 3mA 4 20mA input Command Out of Range threshold 5 25V 0 5 VDC 1 5 VDC input 10 5V 0 10 VDC 2 10 VDC input 21mA 4 20mA input FEEDBACK SIGNAL INPUT...

Страница 11: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 11 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Input Signal Configurations...

Страница 12: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 12 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications...

Страница 13: ...TDC 100 Series AC Digital High Resolution Controller Installation Maintenance Manual 13 07 24 20 www atcontrols com IOM08032 REVISION 01 WIRING DIAGRAMS Special Applications continued...

Страница 14: ...or stable command signal Triac output failure Motor buzzes and overheats Perform appropriate remedy then replace the unit Exposure to water from conduit entrance Exposure to water from unsealed actuat...

Отзывы: