26
Instruction manual TWI 35-130 G/TWI 45-190 G
Specification of concentric roof flue terminal C33
3.9.4 Parallel connections
The table gives the maximum pipe length for parallel systems. The maximum
pipe length depends on the selected diameter.
Warning
Mount flue gas discharge material with a fall of 5 mm per metre towards
the device.
Requirements for flue gas discharge for parallel systems
Use the longest pipe for calculating the pipe length. If, for example, the flue gas
discharge pipe is 10 metres and the air supply pipe is 15 metres, use the 15
metres for calculating the length. Then add the Lequivalent to these 15 metres
for each 90° and 45° bend in both the air supply and the flue gas discharge. All
this will be explained using a practical example.
Practical example of parallel flue gas discharge
Example
The figure shows a TWI 35-130. The device is to be provided with a 25 m
parallel pipe with a diameter of 100 mm and eight 90° bends. An inspection
shall be carried out for compliance of the configuration with the requirements
stated in the table.
3
Installation
Subject
Description
Roof flue terminal set:- 1x Roof flue
terminal (incl. clamping strip)
- 1x Pipe 1000 mm
- 1x Mounting flange
Item no.:
TWI 35-130: 0305 042
(1)
TWI 45-190: 0305 042
(1)
Construction:
Concentrique
Manufacturer:
Muelink & Grol
Type :
M2000 DDV HR-C
Piping material
Construction :
Concentrique
Flue gas discharge:
Thick-walled aluminium with lip-ring sealing
Air supply:
Thin-wall galvanised sheet steel
Pipe diameters
Flue gas discharge:
TWI 35-130: Ø 80 mm
TWI 45-190: Ø 80 mm
Air supply:
TWI 35-130: Ø 125 mm
TWI 45-190:Ø 125 mm
(1) It is not allowed to use any other roof flue terminal. You can order the roof flue terminal mentioning the item
number with A.O. Smith, manufacturer or wholesaler’s.
Device
Diameter
(1)
Maximum running length
L
equivalent
90° bend
L
equivalent
45° bend
TWI 35-130
80
30
3,9
1,1
TWI 45-190
80
20
3,9
1,1
TWI 35-130
100
100
4,6
1,2
TWI 45-190
100
75
4,6
1,2
(1) The given larger diameter can be used if the maximum running length is insufficient. When using a larger
diameter, this shall be used for both the air supply and the flue gas discharge.
Содержание TWI 35-130
Страница 4: ...4 Instruction manual TWI 35 130 G TWI 45 190 G...
Страница 23: ...Instruction manual TWI 35 130 G TWI 45 190 G 23 Device types IMD 0531 R0...
Страница 34: ...34 Instruction manual TWI 35 130 G TWI 45 190 G 4 Conversion to another gas category...
Страница 42: ...42 Instruction manual TWI 35 130 G TWI 45 190 G 8 Shut down...
Страница 52: ...52 Instruction manual TWI 35 130 G TWI 45 190 G Maintenance 10...
Страница 58: ...58 Instruction manual TWI 35 130 G TWI 45 190 G Annex 12...
Страница 61: ...Instruction manual TWI 35 130 G TWI 45 190 G 61...
Страница 62: ...62 Instruction manual TWI 35 130 G TWI 45 190 G...
Страница 63: ...Instruction manual TWI 35 130 G TWI 45 190 G 63...
Страница 64: ...64 Instruction manual TWI 35 130 G TWI 45 190 G 0311935 R0...