37
Servicing should only be performed by a Quali
fi
ed Service Technician
FAULT
CAUSE
CORRECTIVE ACTION
Flue Sensor
The
fl
ue sensor is
disconnected or short.
• Check
the
fl
ue sensor is properly
connected.
• Replace sensor if necessary.
• Measure the resistance of the sensor
and compare the resistance to Table
11.2 on Page 38.
Outlet Sensor
The outlet sensor is
disconnected or short.
• Check
the
fl
ue sensor is properly
connected.
• Replace sensor if necessary.
• Measure the resistance of the sensor
and compare the resistance to Table
11.2 on Page 38.
Memory Error
Control Board Internal Error
• Cycle
Power.
• Replace the control board if
reoccurs.
Table 10. Troubleshooting Chart - Fault Messages Displayed on UIM (Continued.)
Tank Temperature
118°F
Operating Setpoint
185°F
S t a t u s : F l u e S e n s o r
HELP
RESET
A. O. Smith XP
MENU
Tank Temperature
71°F
Operating Setpoint
185°F
S t a t u s : O u t l e t S e n s o r
HELP
RESET
A. O. Smith XP
MENU
Tank Temperature
109°F
Operating Setpoint
130°F
S t a t u s : M e m o r y E r r o r
HELP
RESET
A. O. Smith XP
MENU