26
Servicing should only be performed by a Quali
fi
ed Service Technician
Table 6. Heat Exchanger Cleaning Kits
MODEL
KIT NUMBER
PART NUMBER
COMPONENT
DESCRIPTION
150 - 400
100157627
100140243
Rear Refractory Cover
100162565*
Nylon 4" Wheel Brush*
100162566
3mm Allen Wrench
100162568
1/4" x 24" Drill Extension
500 - 800
100157628
100140243
Rear Refractory Cover
100162565*
Nylon 4" Wheel Brush*
100162567
1/4" x 12" Drill Extension
100162568
1/4" x 24" Drill Extension
Note:
* Do NOT use a metal brush. Only use the kit provided brush or an equivalent replacement nylon
brush.
Figure 7. Rope Gasket - Heat Exchanger Door
Note:
Rope gasket is intended for sealing combustion (see Figure above). If gasket is damaged DO NOT
reuse, the heat exchanger door must be replaced. Consult factory for replacement heat exchanger
door (Kit 100173794 and 100173799).
Check Delta T
1. Check the Delta T using Table 7 below as a reference.
Table 7. Water Heater Pump Applications / Recommended Temperature Rises
MODEL
*PIPE
SIZE
ARMSTRONG
GRUNDFOS
FLOW RATE
(GPM)
LOSS
(FT/HD)
TEMP.
RISE
150
1-1/4"
E8
--
16
16.6
18°F
200
1-1/4"
E8
--
21
11.8
18°F
285
2"
E17
--
30
17.1
18°F
400
2"
E24
--
39
21
18°F
500
2"
E22
--
53
26
18°F
600
2"
E22
--
53
26
22°F
700
2"
--
TP 40-160
63
32
22°F
800
2"
--
TP 40-160
67
31
24°F
Oiled bearing circulators
1. The circulator shipped with the XP Water Heater is water lubricated. No oiling is required.
2. Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s
instructions. Over-oiling will damage the circulator.
ROPE GASKET
CAUTION:
I
F GASKET IS DAMAGED
DO NOT
REUSE, THE HEAT EXCHANGER DOOR
MUST BE REPLACED.