PARAMETER TABLE
This table lists User Interface Module control parameters and where to access them.
Table 4. UIM Parameters
MENU
ACCESS LOCATION/
PARAMETER NAME
USER ACCESS
INSTALLER ACCESS
DISPLAY MODIFY DISPLAY MODIFY
Temperatures Temperatures> Tank Setpoint
YES
YES
YES
YES
Temperatures> Differential
YES
NO
YES
YES
Temperatures> Setpoint Offset
YES
NO
YES
YES
Display
Settings
Display Settings> Backlight Delay
YES
NO
YES
YES
Display Settings> Temperature Units
YES
YES
YES
YES
Display Settings> Backlight Delay
YES
NO
YES
YES
Service
Service>Service Log> CLEAR button
YES
NO
YES
YES
Service> Service Contact Info> Contact
Name
YES
NO
YES
YES
Service> Service Contact Info> Contact
Phone
YES
NO
YES
YES
Circulation
Pumps
Circulation Pumps> DHW Pump Delay
YES
NO
YES
YES
Circulation Pumps> DHW Anti-Seize
YES
NO
YES
YES
Building
Management
Building Management> BMS Tstat Input
YES
NO
YES
YES
Building Management> BMS
YES
NO
YES
YES
Building Management> BMS Type
YES
NO
YES
YES
Building Management> Volts at Min
YES
NO
YES
YES
Building Management> Volts at Max
YES
NO
YES
YES
Building Management> Rate at Min Volts
YES
NO
YES
YES
Building Management> Rate at Max Volts
YES
NO
YES
YES
Building Management> Setpoint at Min
Volts
YES
NO
YES
YES
Building Management> Setpoint at Max
Volts
YES
NO
YES
YES
Building Management> On Volts
YES
NO
YES
YES
Building Management> Off Differential
Volts
YES
NO
YES
YES