T-H2-DV/T-H2-OS Service Manual
Ver. 1.01
61
CONFIDENTIAL
<Description of mode numbers in “Diagnostics Mode” for whole unit in Easy-link system>
Diagnostics information
3-digit 7-seg LED on the
computer board
TM-RE30
Mode
#**
Whole easy-link system
information (#0)
Mode
#**
Whole easy-link system
information (#0)
Total system flow rate
h1 0.0 to 99.9 GPM
h1 0 to 9,999 (×0.1 GPM)
BTU requirement for the
Easy-link system
h2 0 to 999 (×1,000 BTU/h)
h2 0 to 9,999 (×100 BTU/h)
Quantity
of
connected
T-H2-DV/T-H2-OS’s
h3 1 to 4 (units)
h3 1 to 4 (units)
Priority T-H2-DV /T-H2-OS unit h4 1 to 4 (unit #)
h4 1 to 4 (unit #)
Quantity
of
operational
T-H2-DV/T-H2-OS’s
h5 1 to 4 (units)
h5 1 to 4 (units)
Set temperature
h6 100 to 185 °F
h6
Operation time during current
rotation
h7
0 to 720 (minutes). After
720, the next rotation
occurs
h7 0 to 720 (minutes). After 720,
the next rotation occurs
ON/OFF cycles during current
rotation
h8 0 to 100 (cycles). After 100,
the next rotation occurs
h8 0 to 100 (cycles). After 100,
the next rotation occurs
N/A
h9
N/A
h9
N/A
h10
h10
h11
h11
Inlet temperature of the
priority unit
h12 32 to 212
˚
F
h12 32 to 212
˚
F
Mixing temperature of the
priority unit
h13 32 to 212
˚
F
h13 32 to 212
˚
F
N/A
h14
N/A
h14
N/A
h15
h15
Activation of freeze protection
pump
P1 OFF or ON (Default:OFF)
P1
N/A
Activation of detection for
pump error
P2 OFF or ON (Default:OFF)
P2
Activation of pump test
operation
P3 Pon***
P3
NOTE: The “h1” to “h15” can be selected only in parent unit.
***When the dipswitch No.4 (the right bank) on the T-H2-DV/T-H2-OS computer board is set to the
“OFF” position, press and hold the “Number display” button on the computer board while in
mode# P3 for at least 3 seconds to display the “Pon”. Then, turn off the TM-RE30. “Pon” means
pump test operation is in the “ON” mode.