11.1.1
General errors
Note
For the coding of the connections, refer to the Electrical wiring diagram.
Indication
Cause
Measure
Gas smell
There is a gas leak
Close the mains gas valve at once.
Do not operate any switches.
No naked flames.
Ventilate the boiler room.
Immediately contact your installation
engineer or your local gas company.
•
•
•
•
•
The display is off
The water heater is off.
Turn on the water heater (see section 4.1).
There is no supply voltage.
Make sure that:
the control switch is set to I.
the isolator is in ON position.
there is power on the isolator.
there is power to the electrical connector
block.
The measured voltage must be
230 V
AC
(-15%, +10%).
•
•
•
•
Defective fuse(s)
Replace the fuse(s).
Water leakage
There is a leakage from a threaded
water connection.
Tighten the threaded connection.
There is a condensate leakage
Make sure that the condensation water
discharge is working properly.
If necessary, correct the water discharge.
There is a leakage from another nearby
water heater or pipe segment.
Trace the leakage.
There is a leakage from the water heater
tank.
Contact the supplier of your water heater.
Explosive ignition
The gas supply pressure is incorrect.
Check the gas supply pressure, refer to Gas
supply pressure.
The CO
2
value is incorrect.
Check the CO
2
value, refer to CO
2
value.
The burner is contaminated.
Clean the burner, refer to Gas-side
maintenance (see section 10.3).
There is an air leakage between the
venturi and the flexible air connector.
Make sure that:
the flexible air connector is not damaged.
If necessary, replace the flexible air
connector.
the flexible air connector is correctly
connected to the venturi.
If necessary, tighten the clamp.
•
•
n
96
Installation, Maintenance and Service part
Содержание SGS-28
Страница 6: ...6 ...
Страница 13: ...User part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 13 ...
Страница 14: ...14 ...
Страница 16: ...16 User part ...
Страница 18: ...18 User part ...
Страница 24: ...24 User part ...
Страница 40: ...40 User part ...
Страница 41: ...Installation Maintenance and Service part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 41 ...
Страница 42: ...42 User part ...
Страница 82: ...82 Installation Maintenance and Service part ...
Страница 90: ...90 Installation Maintenance and Service part ...
Страница 104: ...104 Installation Maintenance and Service part ...
Страница 110: ...Fig Dimensions SGS 28 30 50 60 110 Installation Maintenance and Service part ...
Страница 112: ...Fig Dimensions SGS 80 100 120 112 Installation Maintenance and Service part ...
Страница 121: ...12 8 Declaration of conformity 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 121 ...
Страница 124: ...124 Installation Maintenance and Service part ...
Страница 126: ...126 Installation Maintenance and Service part ...