Condensate Pump Troubleshooting

A condensate pump may be necessary if the drain 
point is above the level of the condensate drain 
on the heat pump water heater. A condensate 
pump failure detect is provided with the heat pump 
water heater control. Follow the instructions in the 
installation and operation manual for connection 
of the condensate pump failure switch to the heat 
pump control.

Should the condensate pump fail to operate and 
clear the condensate from the pump reservoir, the 

fl

 oat switch provided with the pump will open. The 

heat pump control will detect condensate pump 
failure and shut off the heat pump in order to stop 
condensate from being produced. “HEAT PUMP 
FAULT” will be displayed on the user interface 
and the heat pump will not operate until the fault 
is cleared. By checking the MAINTENANCE 
DISPLAY, the fault can be narrowed down. For 
a condensate pump failure, the MAINTENANCE 
DISPLAY will indicate CONDENSATE DRAIN 
ALARM.

In order to determine the cause of the condensate 
drain alarm, 

fi

 rst ensure that the condensate pump 

has power. Check that the condensate pump is 
plugged into an outlet and that the socket that the 
condensate pump is plugged into is powered. If the 
pump has power, check the outlet tubing for clogs 
or kinks that could prevent 

fl

 ow of condensate. 

Also check the pump inlet in the sump for debris 
that might block 

fl

 ow. Follow the condensate pump 

manufacturer’s instructions for seperating the pump 
section from the tank.

If condensate pump appears to be functioning 
properly but is unable to clear the condensate from 
the tank, make sure the height of the discharge 
point does not exceed the pump manufacturer’s 
speci

fi

 cation. Consult the manufacturer’s literature 

for this information.

Condensate Drain Maintenance

Condensate may be produced when the heat pump 
runs, depending on the amount of humidity in the 
air. If the relative humidity is high, the amount 
of condensate can exceed 20 oz per hour. The 
condensate is collected in a plastic pan under 
the evaporator. Two drain ports are provided for 
connection of primary and secondary drain lines. 
1/2 inch PVC is recommended for connection to the 
drain ports. The condensate pan, drain ports and 
lines should be inspected and cleaned periodically. 
Shut off power to the appliance before performing 
any maintenance or repair. Access to the drain 
pan can be gained by removing right side of louver 
panel. The black plastic pan is inside located below 
the evaporator and the two drain ports are located 
toward the back of the unit. Wipe the inside of the 
condensate pan with a clean rag to remove any 
debris or algea that may be present. Use an old 
toothbrush or a bottle brush to clean the inside of 
the two drain ports. Flush the ports with a small 
amount of clean water. Clean the condensate 
pump, if one is installed, in accordance with the 
manufacturer’s instructions.

Disposal of Condensate 

Condensate should be disposed of in accordance 
with any applicable local codes that may exist. 
Guidelines for HVAC systems are applicable to the 
heat pump water heater.

Inspection/Cleaning of the Condensate Drain Pan & Condensate Drain 
Lines

IMPORTANT:

 Before attempting to clean or replace the condensate drain pan or lines press the power button to 

place the water heater in Standby Mode and shut-off power to the water heater at the circuit breaker/fuse box.
1.  Remove the access panel (fan side) by loosening the screws securing it to the unit. 
2.  Check the condensate drain pan and drain lines for any dirt or debris that might interfere with proper drainage. 

Wipe out any dirt or debris with a damp cloth.

3.  Once the condensate drain pan and lines have been inspected/cleaned, secure the access panel to the water 

heater.

4.  Restore power to the water heater and press the power button to turn the water heater on. 

NOTE:

 The water heater will conduct an eight (8) minute system diagnostic prior to operation. 

Содержание PHPT-60

Страница 1: ...R Service Handbook PRINTED IN THE U S A 0511 321547 000 SERVICE SHOULD ONLY BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN FOR MODELS PHPT 60 60 GAL PHPT 80 80 GAL INSTALLATION CONSIDERATIONS PREVENTI...

Страница 2: ...ection B 16 Control Board Section C 17 Control Board Section D 18 Wiring Diagrams 19 20 Accessing Maintenance Display 21 Element Test Continuity Check 22 Element Test Ohm s Check 23 Heating Element Re...

Страница 3: ...tial that you return the unit to a safe condition before you leave the site All original components must be re installed and all safety measures must be implemented In addition the recommended water t...

Страница 4: ...ed The volume and pressure of water increases when it is heated in a closed system IE Water heated from 90 F to 140 F in a 40 gallon water heater will expand by approximately one half gallon Minerals...

Страница 5: ...SHUO VL HG WHPSHUDWXUH SUHVVXUH UHOLHI YDOYH PXVW EH LQVWDOOHG LQ RSHQLQJ SURYLGHG DQ UHVXOW LQ RYHUKHDWLQJ DQG H FHVVLYH WDQN SUHVVXUH DQ FDXVH VHULRXV LQMXU RU GHDWK WARNING Excessive Weight Hazard...

Страница 6: ...ll piping properly installed and free of leaks Heater completely filled with water see Water Piping System section p 9 Closed system pressure buildup precautions installed see Closed System Thermal Ex...

Страница 7: ...ser Interface Module UIM The unit is in Standby the power button on the UIM is RED Press the power button it should turn green and the display should light up If the power button does not turn green r...

Страница 8: ...erode over time and become less effective until they stop working all together another type of protective device is a powered anode A powered anode is an active device that counteracts galvanic corros...

Страница 9: ...of joint compound and be certain that all fittings are tight IMPORTANT DO NOT over apply joint compound Piping Installation 1 Install the water piping and fittings as shown Figure 2 Connect the cold...

Страница 10: ...sure Relief Valve Drain Line 3 4 19mm ID Minimum Drain Figure 3 Temperature and Pressure Relief Valve Installation For protection against excessive pressures and temperatures a temperature and pressur...

Страница 11: ...upper thermostats Routine Preventive Maintenance At least monthly a visual inspection should be made of the following Air Filter Remove and inspect clean if needed and reinstall Condensate drain pan...

Страница 12: ...sed in this mode The key advantage of using this mode is that it eliminates the cool air exhausted from the heat pump During cold weather months this may be desirable Hot water delivery and operating...

Страница 13: ...upon completion of service work Selecting Operating Mode The operating mode can be changed by touching the desired mode icon on the User Interface Module Figure 4 NOTE While vacation mode is on the o...

Страница 14: ...d reports any errors through the User Interface Module UIM Based on the inputs from the sensors and or the manual inputs from the UIM the Control Board determines which heating mode the unit should be...

Страница 15: ...onnect to lower heating element Pin 2 Connect to L1 behind ECO switch CN 206 Compressor Pin 1 Compressor power L1 Pin 2 Unused Pin 3 Unused Pin 4 Compressor power L2 CN 207 Fan Low high Pin 1 Fan powe...

Страница 16: ...l 1 COM Connects to L1 behind the ECO Switch Terminal 2 NO Connects to the upper heating element CN 203 Powered Anode Pin 1 Powered anode signal Pin 2 Ground Figure 7 Terminal 1 Terminal 2 Pin 2 Pin 1...

Страница 17: ...Pin 3 Lower water temperature sensor on tank Pin 4 Lower water temperature sensor on tank CN 212 Temperature Sensors Pin 1 Ambient temperature sensor Pin 2 Ambient temperature sensor Pin 3 Discharge t...

Страница 18: ...verflow optional Note Pin 9 and 10 are connected by a jumper wire This wire should be cut and wired in series to the overflow switch of the field supplied condensation pump optional SW 201 Dip Switch...

Страница 19: ...ER ELEMENT OVERLOAD DETECTION ANODE POWERED HP TEMP TANK TEMP COMPRESSOR DISPLAY USER INTERFACE UPPERELEMENT 4 5 KW NOTES 1 THEFUNCTIONOF CN211 AND CN215 IS THE SAME EITHER CN211 OR CN215 SHOULD BE CO...

Страница 20: ...ring Diagram for Non Relay Models L1 L2 Red Black Approved Connectors Junction Box Overload Protectio To 240v 1 Phase Power supply Electrical Service ground Circui Breaker Ground Wire Green n t FIigur...

Страница 21: ...temperatures and the final four 4 show the fault code history The down arrow can be used to access previous screens Table 2 Maintenance Display Screen Message Meaning 1 Ambient Temperature Air tempera...

Страница 22: ...for a Grounded Element IIB Testing for a Grounded Element 1 Complete Preparing for the Test before you proceed 2 Check for continuity as follows A Place a test probe on one of the element terminals an...

Страница 23: ...grounded If either test shows less than infinite resistance the element is defective and should be replaced p 24 D Proceed to Completing the Test III Completing the Test 1 Replace the element s if ne...

Страница 24: ...element by loosening the screws Figure 14 Remove the screw in element by turning the element counterclockwise with a 1 1 2 inch socket wrench Remove the existing gasket 8 Clean the area where the gas...

Страница 25: ...and the water heater should return to normal operation If resetting the ECO does not clear the error the ECO will need to be checked Follow the procedure below NOTE Tank temperature must be less than...

Страница 26: ...it measures 25uF 5 it is good If the value is outside this tolerance the capacitor is bad and should be replaced If a capacitance meter is not available use an Ohm meter to check the condition of the...

Страница 27: ...ded period of time If power must be turned off drain the tank completely to minimize corrosion Removing the Powered Anode 1 Press the power button on the UIM to place the water heater in Standby Mode...

Страница 28: ...ress power button and verify that unit is in efficiency mode Raise set point 10 Wait ten 10 seconds for compressor to turn on Perform voltage and current checks Fan on Hot Cool No Fan on No Yes Yes Ta...

Страница 29: ...Done No Bad Good Check resistance from anode center tab to tank 1M Bad Remove anode and check resistance from threaded portion of anode to the tab 1M Bad Replace anode Good Check that upper element i...

Страница 30: ...es Hot Yes No Replace fan Check filter and evaporator for dirt and dust build up Bad 100 Good Motor thermal switch may be open allow to cool Repeat resistance check Replace fan 100 49 61 Reconnect CN2...

Страница 31: ...e Yes No Check resistance on fan cable connector pin 1 to 3 Good 49 61 Bad 100 Is case of motor hot No Yes Thermal switch may be open allow to cool Check resistance of cold motor Bad 100 Good 49 61 Re...

Страница 32: ...ed and the fault is cleared NOTE After the problem is resolved a fault must be cleared by turning off power to the unit at the breaker or fuse panel for ten 10 seconds and then turning it back on Temp...

Страница 33: ...120 140 160 180 200 220 Temperature F Resistance k Ohms Chart 1 Resistance vs Temperature for Tank and Discharge thermistors 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 0 20 40 60 80...

Страница 34: ...40 41 42 43 44 45 47 49 51 52 54 56 PSIG 54 56 58 60 62 64 66 68 70 72 74 76 78 F 57 59 60 62 64 65 66 68 69 71 72 73 75 PSIG 80 85 90 95 100 105 110 115 120 125 130 135 140 F 76 79 82 85 88 90 93 96...

Страница 35: ...re below for best results 1 Shut off power to the unit at the breaker or fuse box prior to servicing the unit 2 Remove the air inlet and outlet grills Important Do not spray cleaner on the fan motor F...

Страница 36: ...st procedure p 32 replace sensor if defective Inlet or outlet water valves at the water heater closed Insure valves are fully open INSUFFICIENT HOT WATER SLOW HOT WATER RECOVERY Temperature set point...

Страница 37: ...ntinue use of re circulation system Hot water leak at faucet or piping Repair hot water leaks Sediment or scale build up in tank Drain and flush tank Water conditioning may be required to minimize bui...

Страница 38: ...cing the water heater DRIPPING DRAIN VALVE Valve may be slightly open Check to see if the drain valve is closed tightly If the leakage cannot be stopped by tightening the valve replace it WATER DISCOL...

Страница 39: ...er and void the warranty Control board faulty If the error still persists this problem may be caused by the control board Replace the control board Heat Pump Connect Fault Heat pump compressor circuit...

Страница 40: ...lue If the measured resistance is 200k or 0 the thermisitor is faulty Replace thermisitor assembly Control board faulty Replace control board If replacing the control board doesn t resolve the issue c...

Страница 41: ...Lower pressure switch is open Low suction pressure Use a service gage set to check system pressures high and low sides The low side pressure switch opens if suction pressure drops below 7 3 psi and wi...

Страница 42: ...OM Fault Main board failure Faulty control board Replace the control board If replacing the control board doesn t resolve the issue contact technical support Main Control Board EEPROM Fault Main board...

Страница 43: ...shorted the ECO is good if not the ECO is faulty and should be replaced Condensate Drain Alarm The installed condensate pump is not working Condensate pump not operating Check to see if condensate pum...

Страница 44: ...lowchart p 29 Low water level Check water level fill the tank if necessary Power Anode No Current Sense Powered anode circuit not working Faulty control board Replace the control board If replacing th...

Страница 45: ...he tank open the cold water inlet valve and restart the heater IMPORTANT Do not turn on power to the water heater unless it is completely filled with water To ensure that the tank is full open a hot w...

Страница 46: ...midity in the air If the relative humidity is high the amount of condensate can exceed 20 oz per hour The condensate is collected in a plastic pan under the evaporator Two drain ports are provided for...

Страница 47: ...ls 9007324005 14 Air Filter 9007482005 15 Compressor Wiring Harness 409171 000 16 Fuses 2 Input power to control board 3 Amp 250V slow blow 20mm X 5mm 9007485015 17 T P Valve 9000728015 18 Drain Valve...

Страница 48: ...48 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2011 Inc All Rights Reserved...

Отзывы: