10

paragraph. The new valve must be marked with a maximum set 

pressure not to exceed the marked hydrostatic working pressure 

of the water heater (150 psi = 1,035 kPa) and a discharge capacity 

not less than the water heater Btu/hr or KW input rate as shown on 

the water heater’s model rating plate.

For safe operation of the water heater, the temperature and pressure 

relief valve must not be removed from its designated opening nor 

plugged. The temperature-pressure relief valve must be installed 

directly into the fitting of the water heater designed for the relief valve. 

Install discharge piping so that any discharge will exit only within 6 

inches (15.2 cm) above, or at any distance below the structural floor. 

Be certain that no contact is made with any live electrical part. The 

discharge opening must not be blocked or reduced in size under 

any  circumstances.  Excessive  length,  over  30  feet  (9.14  m),  or 

use of more than four elbows can cause restriction and reduce the 

discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve 

and the tank. Do not connect discharge piping directly to the drain 

unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, 

hazard to life, or property damage, the relief valve must be allowed 

to  discharge  water  in  adequate  quantities  should  circumstances 

demand. If the discharge pipe is not connected to a drain or other 

suitable means, the water flow may cause property damage.

The Discharge Pipe:

• 

Shall not be smaller in size than the outlet pipe size of the valve, or 

have any reducing couplings or other restrictions.

• 

Shall not be plugged or blocked.

• 

Shall be of material listed for hot water distribution.

• 

Shall be installed so as to allow complete drainage of both the 

temperature-pressure relief valve and the discharge pipe.

• 

Must terminate a maximum of six inches above a floor drain or 

external to the building. In cold climates, it is recommended that the 

discharge pipe be terminated at an adequate drain inside the building.

• 

Shall not have any valve or other obstruction between the relief 

valve and the drain.

The temperature-pressure relief valve must be manually operated 

at least once a year. Caution should be taken to ensure that (1) no 

one is in front of or around the outlet of the temperature-pressure 

relief valve discharge line, and (2) the water manually discharged 

can  cause  bodily  injury  or  property  damage  because  the  water 

may be extremely hot. If after manually operating the valve, it fails 

to  completely  reset  and  continues  to  release  water,  immediately 

close the cold water inlet to the water heater, follow the draining 

instructions in this manual, and replace the temperature-pressure 

relief valve with a properly rated/sized new one. 
If you do not understand these instructions or have any questions 

regarding  the  temperature-pressure  relief  valve  call  the  toll  free 

number listed on the water heater label for technical assistance.

CLOSED WATER SYSTEMS

Water supply systems may, because of code requirements or such 

conditions  as  high  line  pressure,  among  others,  have  installed 

devices such as pressure reducing valves, check valves, and back 

flow preventers. Devices such as these cause the water system to 

be a closed system.

THERMAL EXPANSION

As water is heated, it expands (thermal expansion). In a closed system 

the volume of water will grow when it is heated. As the volume of 

water grows there will be a corresponding increase in water pressure 

due to thermal expansion. Thermal expansion can cause premature 

tank failure (leakage). This type of failure is not covered under the 

limited  warranty. Thermal  expansion  can  also  cause  intermittent 

temperature-pressure relief valve operation: water discharged from 

the valve due to excessive pressure build up. This condition is not 

covered under the limited warranty. The temperature-pressure relief 

valve is not intended for the constant relief of thermal expansion.
A properly sized thermal expansion tank should be installed on all 

closed systems to control the harmful effects of thermal expansion. 

Contact a local plumbing service agency to have a thermal expansion 

tank installed.

Содержание Lowboy 6

Страница 1: ...FUTURE REFERENCE COMMERCIAL LIGHT DUTY ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products Lowboy 6 10 15 20 Models Series 102...

Страница 2: ...ition to electrical testing skills when performing service ANSI Z223 1 2006 Sec 3 3 83 Qualified Agency Any individual firm corporation or company that either in person or through a representative is...

Страница 3: ...ment grounding terminal or lead on the water heater HYDROGEN GAS FLAMMABLE Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a long period of time gen...

Страница 4: ...rical Code CSA C22 1 The National Electrical Code may be ordered from National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 The Canadian Electrical Code is available from the Canadi...

Страница 5: ...53 138 128 115 110 5000 5000 GPH 113 101 75 68 56 51 45 41 38 34 32 10 LPH 426 384 284 256 213 192 170 153 142 128 122 6000 6000 GPH 135 122 90 81 68 61 54 49 45 41 39 12 LPH 511 460 341 307 256 230 2...

Страница 6: ...6 APPROVALS MODEL AND RATING Lowboy 30 40 50 Tall 30 40 52 66 80 120 Lowboy 6 10 15 20 All models are listed by Underwriters Laboratories Inc...

Страница 7: ...ION INSTALL IN ACCORDANCE WITH ALL LOCAL CODES INSTALL VACUUM RELIEF IN COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES INSTALL SUITABLE DRAIN PANS UNDER WATER HEATERS TO PREVENT DAMAGE DUE TO LEAKAG...

Страница 8: ...metimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector...

Страница 9: ...imum of 120 degree F Consult a qualified installer or service agency Follow all manufacturer s Instructions for installation of these valves Before changing the factory setting on the thermostat read...

Страница 10: ...ated at an adequate drain inside the building Shall not have any valve or other obstruction between the relief valve and the drain The temperature pressure relief valve must be manually operated at le...

Страница 11: ...on J terminal to L1 It is then possible for both elements to operate at once as determined by the thermostats Regardless of element connection the heater operates in an unbalanced fashion The heater...

Страница 12: ...12 Figure 3 WIRING DIAGRAMS C 2 CIRCUIT FOR Lowboy 6 10 15 20 HEATERS EQUIPPED WITH HIGH LIMIT CONTROL A 8 CIRCUIT FOR DUAL ELEMENT HEATER FACTORY WIRED FIELD WIRING WHITE FOR 120V 277V...

Страница 13: ...lso check connections on top and or sides of heater Repair water leaks and tighten electrical connections as necessary 3 Depress the red manual reset button on each Thermostat ECO combination control...

Страница 14: ...MED and HI See Figure 5 The approximate equivalent temperatures for these three settings are LO 140 F 60 C MED 160 F 71 C and HI 181 F 83 C These thermostats are set from the factory at the LO 140 F 6...

Страница 15: ...y the anode rod This does not affect water s taste or color The rod must be maintained to keep tank in operating condition Anode deterioration depends on water conductivity not necessarily water condi...

Страница 16: ...le accumulations on the elements causes sizzling and hissing noises when the heater is operating The sounds are normal however the tank bottom and elements should be cleaned See the Maintenance sectio...

Страница 17: ...ary to shut off electricity and drain tank to perform procedure Water leaks at the elements may be due to 1 Defective element which leaks at terminals or thru flange Replace element 2 Loose element ga...

Страница 18: ...d by improper gas supply line sizing gas type venting connections combustion air voltage wiring or fusing Failure to follow applicable codes Failure to follow printed instructions Abuse misuse acciden...

Страница 19: ...19 NOTES...

Страница 20: ...r parts will be shipped at prevailing prices and you will be billed accordingly The model number of your Water Heater will be found on the rating plated located above the lower access panel Be sure to...

Страница 21: ...3307 000 043307 000 043307 000 7 Personnel Protector 9003914015 9003914015 9003914015 9003914015 8 Pipe Nipple 194130 194130 3 194130 3 194130 3 9 Plate Knockout 43293 1 43293 1 43293 1 43293 1 PLUG 1...

Страница 22: ...57015 9002857015 9002857015 9002857015 9002857015 9002857015 9002857015 7 Thermostat Bracket each 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 9003898215 8 P...

Страница 23: ...9002874005 9002875005 TABLE 7 INCOLOY SHEATH ELEMENT AND WATTAGE CHART K W ELEMENT WATTAGE 120 V 208 V 240 V 277 V 480 V PART NO PART NO PART NO PART NO PART NO 1 5 1500 W 9004279005 9004283005 900429...

Страница 24: ...24...

Отзывы: