background image

h

1'

H'

Jv'>

rh

HYORONIC

BALANCER

.'-',I

hS

GAS

r

~

r

;h'h

Where

an

exhaust

fan

is

installed

in

the

same

LEVELLING

room

with

a

boiler,

sufficient

openings

for

air

must

be

provided

In

the

walls.

Undersized

open-

The

boiler

should

be

checked

during

and

after

ings

will

cause

air

to

be

drawn

into

the

room

installation

to

be certain

that

it

is

level.

JI

through

the

chirn.ney,

causing

poor

combustion.

Scoting

may

result

in

serious

damage

to

the

If

the

unit

is

not

level,

shims

should

be

inserted

boiler.

under

the

unit

to

correct

this

condition.

INSTALLATION

CLEARANCES

WATER

LINE

CONNECTIONS

(Fig.

1)

These

units

are

listed

for

installation

with

the

following

minimum

clearances:

In

all

cases,

local

codes

have

authority

over

the

I.'

following

Instructions:

6"

between

sides

and

rear

of

unit

and

combustion

construction.

1.

Supply

and

Return

Lines.

Be

sure

that

sys-

tem'supply

and

return

lines

are

connected

to

24"

should

be

provided

at the

front

of the

unit

for

the

proper

boiler

connections,

fig.

1,

to

pro-

proper

servicing.

In

a

utility

room

installation,

vide

up flow

of water

through

the

boiler.

the

door

shall

be

wide

enough

toallow

the

bolter

to

enter

or

to

permit

the

rdplacement

of

another

2.

Hydronic

Balancer.

Piping

in fig.

1 includes

appliance

such

as

a water

heater.

a

hydronic

balancer

by-pass

between

supply

and

return

lines.

This

will

permit

adjustment

It

is

recommended

that

sufficient

area

be

left

at

to

provide

an

adequate

minimum

flow

rate

y

rear

of

these

units

for

servicing.

through

the

boiler

with

certain

variable

flow

rate

zoned

systems.

This

valve

should

be

AII

models

may

be

installed

on

combustible

opened

only

enough

to

stabilize

the

boiler

flooring.

controls

when

only

the

smallest

zone

is

In

operation.

CONVENTIONAL

INSTALLATION

t

PIPEHANGERS

MAIN

PFLOT

EXPANSION

TANK

MANUAL

SHUTOFF

SliUTOFF__

VALVE

VALVE

AIR

VALVE

TANK

SEPARATOR

I

FITTING

flFUSED)

I

SYSTEM

~

<

H TOFF

SUPPt,y

HELIEFVALVE

'

VALVE

UNE

(PIPEDTOOPENDRAIN)

I;-'

CIRCULATOR

SYSTEM

RETURN

5

THERALTNETER

INSTALL

INACCORDANCE

WITH

LOCAL

CODES

LWE

'DRAIN

VALVE

NATER

OUTLET

*NOTE:DRAIN

VALVEANDGATEVALVE

*GATE

VALVE

SHOWN

BELOW

CIRCULATOR

ARE

FLOWSWITCH

I~II

IP

FORPRESSURE

PURGING,

IF

JI

j

HElGHT(FOLLOW

OESlaED.

BY-PASS

3

THERM0METER

>

1

I'

I

LOCALCODES)

RFAE

LIMITCONTROL

(MANUAL

SESEn

PRESSURE
REQUCING

-5"

I" MINIMuM

COLD

WATER

VALVE

ORAIN

I.'::

SUPPLY

WATER

INLET

FIGURE 1

AOS121

5

Roenbeck

FILED: NEW YORK COUNTY CLERK 02/20/2018 10:20 AM

INDEX NO. 190311/2015

NYSCEF DOC. NO. 337

RECEIVED NYSCEF: 02/20/2018

Содержание HW-160

Страница 1: ...NTIAL TYPE HYDRONIC BOILERS models HW 160 HW 200 HW 225 with FIA I ll PLAINTIFPS EXHIBIT a century Forwaitl IV LI S A PRINTEDI 3399 I PART NO 76033 374 Raenbeck FILED NEW YORK COUNTY CLERK 02 20 2018...

Страница 2: ...00 HW 225 A 49 1 8 51 1 4 60 1 4 29 3 8 32 3 8 32 3 8 C 24 1 4 27 1 8 27 1 8 D 20 3 4 20 3 4 20 3 4 E 5 1 2 5 1 2 5 1 2 F 8 8 8 G 16 1 4 16 1 4 16 1 4 H 7 7 7 J 35 3 4 35 3 4 35 3 4 K 32 32 32 L 1 1 4...

Страница 3: ...size piping conditions exist reduce ratings by 10 gc CIRCULATOR EXPANSION TANK SELECTIONS The following circulators are required to provide The diaphragm type expansion tank sizes listed proper water...

Страница 4: ...an area where it provided will not be subject to freezing temperatures AIR REQUIREMENTS Confined Space An ample supply of air must be provided for proper combustion An insufficient supply of air will...

Страница 5: ...t the replacement of another 2 Hydronic Balancer Piping in fig 1 includes appliance such as a water heater a hydronic balancer by pass between supply d and return lines This will permit adjustment It...

Страница 6: ...and sys pump as Instructed on the oil tube supplied tema requiring pressure purging should be with the unit fig 8 Installed with by pass piping around the pressure reducing valve ha 4 Vent Valves It...

Страница 7: ...rnetal type remove the regulator cap on underside of gas valve and turn the adjusting screw counter To trap any dirt or foreign material in the main clockwise to decrease the pressure Turn gas line a...

Страница 8: ...nector plus 50 of the areas chimney with oil or coal burning equipment of the additional flue or vent connector This practice is prohibited by many local WIRING CONNECTl0NS All electrical work must be...

Страница 9: ...VIEY LIMI RESET FLOW SWITCH O O 1 2 3 4 5 6 7 8 9 10 11 12 HIGH TEMP WIAE FLAME ROO P LO SAFETYSHUT OFFVALVE LOW GAS PRESSURE I SWITCH HfGH GAS THERMCCOUPLE PRESSURE SWITCH FACTORY W1RED FIGURE 4 FACT...

Страница 10: ...ONEYWELL a RA832A RA832A 5 RELAY 5 RELAY THERMAL THERMAL BALANCER y See BALANCER y L o O t T T T T R adam R fame a 2 1 3 4 2 1 3 4 W W PUMP Ihiia 4 X 4 JUNCTION BOx P EiLi DELAY WITHTERMINALSTRIP 85 O...

Страница 11: ...ER PANEL SE EFIG 4 FIGURE 7 ZONED SYSTEM HONEYWELL ZONE VALVES 4 4 2 4 T 24 ERMOSTAT VOLT F I 2 2 2 2 2 2 2 2 2 2 40VATRANSFORMER T 3 3 1 3 1 3 I 3 1 3 TOHANOLE UP 70 2 5ZONE VALVES ZCNE VALVES LW R T...

Страница 12: ...so can produce acid concentrations of the following methods that become corrosive cause gases to form that block water circulation or lead to formation of With an acid pump or hand pump deposits on t...

Страница 13: ...ION Make sure heater is filled with water TONexreANE before lighting pilot The main man J 2SED PUMP ual gas shutoff valve and pilot ad ___ay Eu OW ____ justing valve located near main an __ __ _____ b...

Страница 14: ...an orange 90 seconds quality in the flame when used on L P gas This is a normal and approved char After cause of failure has been corrected acteristic the safety switch of the RA 890 relay must be ma...

Страница 15: ...nces should the b gas Input exceed the input shown on If the unit la exposed to the following do not op the boiler rating plate Overfiring crate boiler until corrective steps have been made could resu...

Страница 16: ...indirect heating of salt water or corrosive chemicals b when completely full of liquid free to circulate at all times c at water pressures not exceeding the pressure rating shown on the boiler d with...

Страница 17: ...forwarding the replacement part from the nearest distributor and returning the claimed defective part to such distributar c All cast necessary ar incidental far any materials and or permits required...

Страница 18: ...8 51 1 4 60 1 4 B 29 3 8 32 3 8 32 3 8 C 24 1 4 27 1 8 27 1 8 D 20 3 4 20 3 4 20 3 4 E 5 1 2 5 1 2 5 1 2 F 8 8 8 G 18 1 4 16 1 4 16 1 4 H 7 7 7 J 35 3 4 35 3 4 35 3 4 K 32 32 32 L 1 1 4 1 1 4 1 1 4 M...

Страница 19: ...unusual pick up or large size piping conditions exist reduce ratings by 10 CIRCULATOR EXPANSION TANK SELECTIONS The following circulators are required to provide The diaphragm type expansion tank siz...

Страница 20: ...l be An ample supply of air must be provided for proper Provided combustion An insufficient supply of air will result in a yellow luminous burner flame causing Confmed Space carboning or sooting of th...

Страница 21: ...or to permit the rdplacement of another 2 Hydronic Balancer Piping in fig 1 includes appliance such as a water heater a hydronic balancer by pass between supply and return lines This will permit adju...

Страница 22: ...r la oiled and op tems requiring predsure purging abould be crated by the manufacturer IT MUST BE Installed with by ass piping around the OILED AGAIN BEFORE OPEFIATED Oil pressure reducing valve the t...

Страница 23: ...s lines shall be remove the regulator cap on underside of gas of the metabto metal type valve and turn the adjusting screw counter To trap any dirt or foreign material In the main clockwise to decreas...

Страница 24: ...with oil or coal burning equipment of the additional flue or vent connector This practice is prohibited by many local Periodically examine the venting system for obstructions and or deteriation of ven...

Страница 25: ...TEMP a l RHEE a REARVJEY ANUAL is m RESET FLOW SW1TCH 8 o a o I II 2 5 7 1 11 12 FLAME HIGH TEMP WIAE ROD SAFETYSHUT PlLOT OFFVA WE Rl R LOW GAS PRESSURE SWITCH HIGH GAS THERMOC OUPLE PRESSURE SWITCH...

Страница 26: ...HONEYWELL RA 832A Q RA832A 5 RELAY 5 BEyAY THERMAL THERMAL 8ALANCER y O Q BALANCER g y Q Q 0 R 0 R e 2 1 3 4 O 2 1 3 4 iPUMP ILiii 4 X 4 JUNCTION BOX O AP Ilaiii OELAyl WITHTERMINALSTRIP aa aa SMITHNO...

Страница 27: ...LER PAMEL SEE MG FIGURE 7 ZONED SYSTEM HONEYWELL ZONE VALVES 2 4 2 4 2 4 2 4 THERMOSTAT Z4 VOLT Ii il 2 1 2 2 2 2 2 2 Z 4 4 4 fl 40VATRANSFORM ER 1 3 3 3 T 3 1 3 1 3 TOHANDLE UF TO q a 6ZONE VALVES ZO...

Страница 28: ...re to do so can produce acid concentrations of the following methods that become corrosive cause gases to form that block water circulation or lead to formation of With an acid pump or hand pump depos...

Страница 29: ...lighting pilot The main man ual gas shutoff valve and pilot ad TONEXTANEL I justing valve ocated near main e USEDI guue burner should be closed for at least SLACK YELLOW 5 minutes REO r raNexrpAnat BA...

Страница 30: ...an orange 90 seconds quality In the flame when used on L P gas This is a normal and approved char After cause of failure has been corrected acteristic the safety switch of the RA 890 relay must be man...

Страница 31: ...shown on If the unit is exposed to the following do not op the boiler rating plate Overfiring crate boiler until corrective steps have been made could result in damage or sooting of by a qualified se...

Отзывы: