Anode Rod/Water Odor

Each water heater contains at least one anode rod, which 

will slowly deplete while protecting the glass-lined tank 

from corrosion and prolonging the life of the water heater. 

Once the anode is depleted, the tank will start to corrode, 

eventually developing a leak. Certain water conditions will 

cause a reaction between this rod and the water.  The 

most common complaint associated with the anode rod 

is a “rotten egg smell” produced from the presence of 

hydrogen sulfide gas dissolved in the water. IMPORTANT: 

Do not remove this rod permanently as it will void any 

warranties. The parts list includes a special anode that 

can be ordered if water odor or discoloration occurs. 

NOTE: This rod may reduce but not eliminate water 

odor problems. The water supply system may require 

special aeration or chlorination equipment from a water 

conditioning company to successfully eliminate all water 

odor problems. 
The use of a water softener may decrease the life of the 

water heater tank. 
The anode rod should be removed from the water heater 

tank every 3 years for inspection. The following are typical 

(but not all) signs of a depleted anode rod:
• 

The majority of the rods diameter is less than 3/8”.

• 

Significant sections of the support wire (approx. 1/3 or 

more of the anode rod’s length) are visible.

If the anode rod shows signs of either or both it should be 

replaced.  NOTE: Whether reinstalling  or replacing the 

anode rod, check for any leaks and immediately correct if 

found.
In replacing the anode:
1.  Turn off gas supply to the water heater.
2.  Shut off the water supply and open a nearby hot water 

faucet to depressurize 

the water tank.

3.  Drain approximately 5 

gallons of water from 

tank (Refer to the 

“Draining and Flushing” 

section for proper 

procedures). Close drain 

valve.

4.  Remove old anode rod.
5. Use 

Teflon

®

 tape or 

approved pipe sealant 

on threads and install 

new anode rod.

6.  Turn on water supply 

and open nearby hot 

water faucet to purge 

air from water system. 

Check for any leaks and 

immediately correct any 

if found.

7.  Restart the water heater as directed under the 

“Operating Your Water Heater.” See the “Repair Parts 

Illustration” section for anode rod location.

TEFLON

® 

is a registered trademark of E.I. Du Pont De Nemours and Company

Draining and Flushing                                                

It is recommended that the tank be drained and flushed every 6 
months to remove sediment which may build up during operation. 
The water heater should be drained if being shut down during 
freezing temperatures. To drain the tank, perform the following 
steps:

1.  Turn off the gas to the water heater at the manual gas shut-

off valve.

1.  Move the switch on the gas control valve/thermostat to the 

“OFF” position to turn off the water heater.

2.  Open a nearby hot water faucet until the water is no longer 

hot.

3.  Close the cold water inlet valve.
4.  Connect a hose to the drain valve and terminate it to an 

adequate drain or external to the building.

5.  Open the water heater drain valve and allow all of the water 

to drain from the tank. Flush the tank with water as needed to 
remove sediment.

6.  Close the drain valve, refill the tank, and restart the heater as 

directed in this manual.

If the water heater is going to be shut down for an extended 
period, the drain valve should be left open.

IMPORTANT:

 Condensation may occur when refilling the tank 

and should not be confused with a tank leak.

.

Routine Preventive Maintenance                            

At least annually, a visual inspection should be made of 

the venting and air supply system, piping systems, main 

burner, pilot burner, and flame-arrestor. Check the water 

heater for the following:
• 

Obstructions, damage, or deterioration in the venting 

system. Make sure the ventilation and combustion air 

supplies are not obstructed. 

• 

Clean any dust or debris from the base-ring filter.

• 

Soot and/or carbon on the main burner and pilot 

burner. Contact a qualified technician.

• 

Leaking or damaged water and gas piping.

• 

Presence of flammable or corrosive materials in the 

installation area.

• 

Presence of combustible materials near the water 

heater.

• 

After servicing this water heater, check to make sure 

it is working properly. (See “Operating Your Water 

Heater” section of this manual.)

IMPORTANT: If you lack the necessary skills required to 

properly perform this visual inspection, you should not 

proceed, but get help from a qualified technician.

EXPOSED
SUPPORT
WIRE 

PITTED
ANODE
ROD

EXPOSED
SUPPORT
WIRE 

FIGURE 24.

Содержание High Efficiency 100 series

Страница 1: ...ctrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fi...

Страница 2: ...Installation 17 Important Information About this Water Heater 18 Operating Your Water Heater 19 21 Lighting Instructions 19 Checking the Draft 20 Burner Flames 20 Emergency Shutdown 20 Water Temperat...

Страница 3: ...t water heaters and have a thorough understanding of this instruction manual Service Agency A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing air sup...

Страница 4: ...oid all ignition sources if you smell Natural or LP gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate Maintain required clearances to combustibles Kee...

Страница 5: ...n Valve U Pilot and Main Burner V Flue W Metal Drain Pan X Igniter Wire Y Base Ring Filter Z FV Sensor AA Transformer BB Flue Damper ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS TO VENT TERMINATIO...

Страница 6: ...instructions you should not proceed but have a qualified technician perform the installation of this water heater Massachusetts code requires this water heater to be installed in accordance with Mass...

Страница 7: ...to clean the spill until all ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result...

Страница 8: ...ctor or water shut off device used in conjunction with a piped metal drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in variou...

Страница 9: ...ural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supply Failure to follow these instructions can result in death explosion or carbon monoxide poisonin...

Страница 10: ...in the occurrence of a leak in the system the gas will settle at floor level Basements crawl spaces closets and areas below ground level will serve as pockets for the accumulation of gas Before lighti...

Страница 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Страница 12: ...typical examples of each method Louvers and Grilles In calculating free area for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louver...

Страница 13: ...re certified by CSA International this certification applies to the vent damper device only and does not mean they are certified for use on this water heater U L recognized fuel gas and carbon monoxid...

Страница 14: ...Before connecting a vent to a chimney make sure the chimney passageway is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces...

Страница 15: ...off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperatu...

Страница 16: ...se excessive restriction to water flow is not recommended Use only 95 5 tin antimony or other equivalent solder Any lead based solder must not be used Piping that has been treated with chromates boile...

Страница 17: ...h duct tape 7 Repeat steps 5 and 6 for the hot water outlet pipe 8 Add additional sections of pipe insulation as needed T P RELIEF VALVE T P RELIEF VALVE MANUAL RELIEF LEVER T P RELIEF VALVE INSULATIO...

Страница 18: ...es Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installation Instructions and Use Care Guide Installation Checklist Water Heater Location Wate...

Страница 19: ...ier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control knob Never use tools If the...

Страница 20: ...emperature range of 120 F 140 F 49 C 60 C is recommended by most dishwasher manufacturers The thermostat of this water heater has been factory set at the VAC Vacation position It is adjustable and mus...

Страница 21: ...erature set by the user Vacation Setting The Vacation Setting VAC sets the controller at approximately 70 F This setting is recommended when the water heater is not in use for a long period of time Th...

Страница 22: ...YL YL BN 24VAC V 24VAC BK 120VAC WH 120VAC GR BK 24VAC HOT WH 24VAC NEUTRAL BL RD BL RD YL YL BK 24VAC HOT WH 24VAC NEUTRAL YL 24VAC YL 24VAC TRANSFORMER YL 24 VAC GAS CONTROL VALVE THERMOSTAT FV SENS...

Страница 23: ...ce information at 1 800 527 1953 A temperature limit switch or ECO Energy Cut Off sensor located in the gas control valve thermostat is used to shut off the water heater if the water temperature excee...

Страница 24: ...ting Your Water Heater See the Repair Parts Illustration section for anode rod location TEFLON is a registered trademark of E I Du Pont De Nemours and Company Draining and Flushing It is recommended t...

Страница 25: ...ush down slightly to free the manifold and pilot tube 7 Carefully remove the manifold assembly from the burner compartment NOTE Be sure not to damage internal parts Replacement Parts IMPORTANT The fol...

Страница 26: ...lot before going to the next step FIRST BEND S OTHER FITTINGS NOT SHOWN FOR CLARITY PILOT TUBE SCREWS OLD PILOT IGNITER FLAME SENSOR ASSEMBLY FIGURE 30 7 Push the new pilot tube and igniter wire throu...

Страница 27: ...ssembly door is tightened visually inspect the door gasket between the manifold burner assembly door and the combustion chamber for spaces or gaps that would prevent a seal IMPORTANT Do not operate th...

Страница 28: ...26 NOTE L P Gas systems use reverse left hand threads on the manifold tube 6 Refer to Gas Piping section Figure 5 and disconnect the ground joint union in the gas piping Disconnect the remaining pipe...

Страница 29: ...roubleshooting Table section 2 See Pilot Light Troubleshooting Flowchart section 3 Seat connector firmly in socket 4 Bleed the air from the gas line 5 Check with gas utility company 6 Check with gas u...

Страница 30: ...at COMBUSTION ODORS 1 Insufficient secondary air 2 Flue clogged 3 Heater installed in a confined area 1 Provide ventilation to water heater Check flue way flue baffle and burner 2 Clean locate source...

Страница 31: ...wer switch on the gas control valve to the OFF position and unplug the power cord from the power outlet 1 Attempt to depress the TCO door switch button see figure 27 If the TCO door switch button depr...

Страница 32: ...e electrode flame sense rod replace the igniter pilot assembly Follow the directions on page 27 to re install the burner assembly into the combustion chamber Follow the instructions for lighting on pa...

Страница 33: ...alve Open Is Main Flame Sensed Is Demand for Heat Satisfied Pilot Main Valve De Energize Is Flame Sensed Damper Energizes and Closes Will not light 8 4 flash error code See Corrective Action Table on...

Страница 34: ...List Item No Parts Description 1 DRAFT HOOD 2 FLUE DAMPER 3 FLUE BAFFLE 4 HEAT TRAP COLD SOME MODELS 5 HEAT TRAP HOT SOME MODELS 6 COLD WATER DIP TUBE 7 ANODE ROD 8 TEMPERATURE PRESSURE RELIEF VALVE L...

Страница 35: ...assembly which contains the manifold tube gasket door pilot igniter flame sensor assembly manifold component block with retainer clip thermal switch and pilot tube Natural Gas Low Nox Item 14B Manifol...

Страница 36: ...36 NOTES...

Страница 37: ...37 NOTES...

Страница 38: ...38 NOTES...

Страница 39: ...in accordance with proper sizing techniques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open syst...

Страница 40: ...OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER OR THE INSTALLATION OPERATI...

Отзывы: