background image

18

  Fresh air openings sized correctly with consideration 

given to the blocking effect of louvers and grilles.

  Ductwork is the same cross-sectional area as the 

openings.

Vent Pipe System

Check for proper drafting at the water heater draft hood. 

Refer to the “Checking the Draft” section of this manual for 

the test procedure. If the procedure shows insufficient draft 

is present, please check the following.

  Draft hood properly installed.

  Vent connectors securely fastened with screws and 

supported properly to maintain six inch clearance.

  Vent connector made of approved material and sized 

correctly.

  Vent pipe system installed according to all local and 

state codes or, in the absence of local and state codes, 

the “National Fuel Gas Code”, ANSI Z223.1(NFPA 

54)-current edition.

  Flue baffle properly positioned in the flue tube.

  Check the vent system for restrictions/obstructions 

and check the vent termination height.  Refer to the 

Combustion Air and Ventilation section of this water 

heater manual for specific requirements.

 

Recheck for sufficient combustion air supply.

Water System Piping

  Temperature and pressure relief valve properly installed 

with a discharge line run to an open drain and protected 

from freezing.

  All piping properly installed and free of leaks.

  Heater completely filled with water.

  Closed system pressure build-up devices installed.

  Mixing valve (when applicable) installed per 

manufacturer’s instructions (See Water Temperature 

Regulation section).

Gas Supply and Piping

  Gas type is the same as that listed on the water heater 

rating plate.

  Gas line equipped with shut-off valve, union, and  drip 

leg.

  Use pipe joint compound or teflon tape marked as being 

resistant to the action of petroleum [Propane (L.P.)] 

gases.

  Adequate pipe size and approved pipe material.

  An approved noncorrosive leak detection solution used 

to check all connections and fittings for possible gas 

leaks. Correct any leak found.

IMPORTANT INFORMATION ABOUT THIS WATER HEATER

This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor 

ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation 

errors. Please review the following checklist and make any required installation upgrades or changes.  

Questions? Contact Residential Technical Assistance by referencing the phone number on the front of the Installation 
Instructions and Use & Care Guide.

Installation Checklist                                                  

Water Heater Location

Water heater location is important and can affect system 

performance. Please check the following:

  Installation area free of corrosive elements and 

flammable materials.

  Centrally located with the water piping system (For new 

installations). Located as close to the gas piping and 

vent pipe system as possible.

  Located indoors and in a vertical position. Protected 

from freezing temperatures.

  Proper clearances from combustible surfaces 

maintained and not installed directly on a carpeted floor.

  Provisions made to protect the area from water damage. 

Metal drain pan installed and piped to an adequate 

drain.

  Sufficient room to service the water heater. See 

Clearances and Accessibility section of this manual.

  Water heater not located near an air moving device.

  Is the installed environment dirty (excessive amounts 

of lint, dirt, dust, etc.)?  If so, the base-ring filter located 

on the bottom of the water heater will need to be 

cleaned periodically.  Refer to the Maintenance of your 

Water Heater section of this manual for information on 

cleaning the base-ring filter. 

Combustion Air Supply and Ventilation

Check for sufficient combustion air supply.  Insufficient air 

for the combustion of gas will result in the flame becoming 

“lazy”, thereby allowing heat to build up in the combustion 

chamber.  This excessive heat will cause a thermal switch 

on the door assembly to trip. Is the water heater installed 

in a closet or other small, enclosed space? If so:

  Are there openings for make-up air to enter and exit 

the room/area? 

 

Are the openings of sufficient size?  Remember, if 

there are other gas-fired or air-consuming appliances 

in the same room, you need more make-up air.  Refer 

to the Location Requirements section of this water 

heater manual for specific requirements.

Fresh air not taken from areas that contain negative 

pressure producing devices such as exhaust fans, dryers, 

fireplaces, etc.

   Is there a furnace/air handler in the same room space 

as the water heater?  If so, has a return air duct system 

been attached that exits the room? If so, check for 

leaks on the air duct system. If no air duct system is 

present, correct immediately by contacting a local 

Heating, Ventilation, Air-Conditioning & Refrigeration 

(HVAC-R) authorized service provider. 

  Fresh air supply free of corrosive elements and 

flammable vapors.

Содержание High Efficiency 100 series

Страница 1: ...ctrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fi...

Страница 2: ...Installation 17 Important Information About this Water Heater 18 Operating Your Water Heater 19 21 Lighting Instructions 19 Checking the Draft 20 Burner Flames 20 Emergency Shutdown 20 Water Temperat...

Страница 3: ...t water heaters and have a thorough understanding of this instruction manual Service Agency A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing air sup...

Страница 4: ...oid all ignition sources if you smell Natural or LP gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate Maintain required clearances to combustibles Kee...

Страница 5: ...n Valve U Pilot and Main Burner V Flue W Metal Drain Pan X Igniter Wire Y Base Ring Filter Z FV Sensor AA Transformer BB Flue Damper ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS TO VENT TERMINATIO...

Страница 6: ...instructions you should not proceed but have a qualified technician perform the installation of this water heater Massachusetts code requires this water heater to be installed in accordance with Mass...

Страница 7: ...to clean the spill until all ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result...

Страница 8: ...ctor or water shut off device used in conjunction with a piped metal drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in variou...

Страница 9: ...ural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supply Failure to follow these instructions can result in death explosion or carbon monoxide poisonin...

Страница 10: ...in the occurrence of a leak in the system the gas will settle at floor level Basements crawl spaces closets and areas below ground level will serve as pockets for the accumulation of gas Before lighti...

Страница 11: ...y a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do c...

Страница 12: ...typical examples of each method Louvers and Grilles In calculating free area for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louver...

Страница 13: ...re certified by CSA International this certification applies to the vent damper device only and does not mean they are certified for use on this water heater U L recognized fuel gas and carbon monoxid...

Страница 14: ...Before connecting a vent to a chimney make sure the chimney passageway is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces...

Страница 15: ...off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperatu...

Страница 16: ...se excessive restriction to water flow is not recommended Use only 95 5 tin antimony or other equivalent solder Any lead based solder must not be used Piping that has been treated with chromates boile...

Страница 17: ...h duct tape 7 Repeat steps 5 and 6 for the hot water outlet pipe 8 Add additional sections of pipe insulation as needed T P RELIEF VALVE T P RELIEF VALVE MANUAL RELIEF LEVER T P RELIEF VALVE INSULATIO...

Страница 18: ...es Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installation Instructions and Use Care Guide Installation Checklist Water Heater Location Wate...

Страница 19: ...ier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control knob Never use tools If the...

Страница 20: ...emperature range of 120 F 140 F 49 C 60 C is recommended by most dishwasher manufacturers The thermostat of this water heater has been factory set at the VAC Vacation position It is adjustable and mus...

Страница 21: ...erature set by the user Vacation Setting The Vacation Setting VAC sets the controller at approximately 70 F This setting is recommended when the water heater is not in use for a long period of time Th...

Страница 22: ...YL YL BN 24VAC V 24VAC BK 120VAC WH 120VAC GR BK 24VAC HOT WH 24VAC NEUTRAL BL RD BL RD YL YL BK 24VAC HOT WH 24VAC NEUTRAL YL 24VAC YL 24VAC TRANSFORMER YL 24 VAC GAS CONTROL VALVE THERMOSTAT FV SENS...

Страница 23: ...ce information at 1 800 527 1953 A temperature limit switch or ECO Energy Cut Off sensor located in the gas control valve thermostat is used to shut off the water heater if the water temperature excee...

Страница 24: ...ting Your Water Heater See the Repair Parts Illustration section for anode rod location TEFLON is a registered trademark of E I Du Pont De Nemours and Company Draining and Flushing It is recommended t...

Страница 25: ...ush down slightly to free the manifold and pilot tube 7 Carefully remove the manifold assembly from the burner compartment NOTE Be sure not to damage internal parts Replacement Parts IMPORTANT The fol...

Страница 26: ...lot before going to the next step FIRST BEND S OTHER FITTINGS NOT SHOWN FOR CLARITY PILOT TUBE SCREWS OLD PILOT IGNITER FLAME SENSOR ASSEMBLY FIGURE 30 7 Push the new pilot tube and igniter wire throu...

Страница 27: ...ssembly door is tightened visually inspect the door gasket between the manifold burner assembly door and the combustion chamber for spaces or gaps that would prevent a seal IMPORTANT Do not operate th...

Страница 28: ...26 NOTE L P Gas systems use reverse left hand threads on the manifold tube 6 Refer to Gas Piping section Figure 5 and disconnect the ground joint union in the gas piping Disconnect the remaining pipe...

Страница 29: ...roubleshooting Table section 2 See Pilot Light Troubleshooting Flowchart section 3 Seat connector firmly in socket 4 Bleed the air from the gas line 5 Check with gas utility company 6 Check with gas u...

Страница 30: ...at COMBUSTION ODORS 1 Insufficient secondary air 2 Flue clogged 3 Heater installed in a confined area 1 Provide ventilation to water heater Check flue way flue baffle and burner 2 Clean locate source...

Страница 31: ...wer switch on the gas control valve to the OFF position and unplug the power cord from the power outlet 1 Attempt to depress the TCO door switch button see figure 27 If the TCO door switch button depr...

Страница 32: ...e electrode flame sense rod replace the igniter pilot assembly Follow the directions on page 27 to re install the burner assembly into the combustion chamber Follow the instructions for lighting on pa...

Страница 33: ...alve Open Is Main Flame Sensed Is Demand for Heat Satisfied Pilot Main Valve De Energize Is Flame Sensed Damper Energizes and Closes Will not light 8 4 flash error code See Corrective Action Table on...

Страница 34: ...List Item No Parts Description 1 DRAFT HOOD 2 FLUE DAMPER 3 FLUE BAFFLE 4 HEAT TRAP COLD SOME MODELS 5 HEAT TRAP HOT SOME MODELS 6 COLD WATER DIP TUBE 7 ANODE ROD 8 TEMPERATURE PRESSURE RELIEF VALVE L...

Страница 35: ...assembly which contains the manifold tube gasket door pilot igniter flame sensor assembly manifold component block with retainer clip thermal switch and pilot tube Natural Gas Low Nox Item 14B Manifol...

Страница 36: ...36 NOTES...

Страница 37: ...37 NOTES...

Страница 38: ...38 NOTES...

Страница 39: ...in accordance with proper sizing techniques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open syst...

Страница 40: ...OF PURCHASE OR PROOF OF INSTALLATION DISCLAIMERS NO EXPRESSED WARRANTY HAS BEEN OR WILL BE MADE ON BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY OF THE HEATER OR THE INSTALLATION OPERATI...

Отзывы: