background image

18

TROUBLE SHOOTING (Continued)

PROBLEM

CAUSE

SOLUTION

1) Blower will not run.

A) “ON/OFF” control switch turned off.

Turn switch to the “ON” position.

B)  Blower  unplugged.

Plug blower back into 115 Vac. outlet.

C) No power at outlet.

Repair service to outlet.

D) Thermostat defective.

Replace thermostat.

E) Control harness defective.

Replace control harness.

F) High limit control circuit open.

Replace thermostat.

NOT ENOUGH

G) Blower motor defective.

Replace  Blower Assembly.

HOT WATER

Thermostat problems.
A) Thermostat set too low.

Turn temperature control higher.

B) Thermostat or ECO defective.

Replace thermostat.

Others
A) Heater undersized.

Reduce hot water use.

B) Low gas pressure.

Contact dealer.

C) Incoming water is unusually cold.

Allow more time for heater to reheat.

D) Leaking hot water pipes or fixtures.

Have plumber check and repair leaks.

A) Defective air flow restrictor.

Take unit out of service immediately, call the
manufacturer’s representative.

B) Not enough dilution air to mix with

Proper dilution air must be provided for

VENT PIPE TOO HOT

     flue gases.

combustion  and  dilution  of  flue  temp.

(ABOVE 170°F)

Refer to “INSTALLATION” section.

C) Dilution air too hot for mixing with

Supply air is too hot.  Check for heat sources

     flue gases.

around and/or blockage of dilution air intake.

D) Wrong burner orifice.

Install correct orifice.

A) Dirt in burner ports

Turn off heater and gas, clean burner head.

B) Combustion air path restricted.

Check dilution air intake, exhaust venting, and

YELLOW FLAME

air openings in bottom base pan for
obstructions or blockage.

C) Not enough dilution air for proper

Check dilution air intake for obstructions

     combustion.

or  blockage.

A) Water on the floor under heater.

See “CONDENSATION” section.

B) Water dripping from blower assembly.

Install condensate drain hose (supplied locally)

CONDENSATION

on drain port of rubber boot of blower assembly
or provide a drip “TEE” in the vent pipe to catch
the condensation. See figure 1 and the
Installation of Vent System instructions.

Improperly sealed, hot or cold supply

Tighten  threaded connections.

connections, relief valve, drain valve

WATER LEAKS

or thermostat threads.
Leakage from other appliances or water

Inspect other appliances near water heater.

water lines.
Condensation of flue products.

Refer to “CONDENSATION” section.

Thermal expansion in closed water

Install thermal expansion tank (DO NOT plug

LEAKING T&P

system.

T&P valve).

Improperly seated valve.

Check relief valve for proper operation
(DO NOT plug T&P valve).

HOT WATER ODORS

High sulfate or mineral content in

Drain and flush heater thoroughly then refill.

(Refer to CATHODIC

water supply.

PROTECTION

Bacteria in water supply.

Chlorinate water supply.

WATER TOO HOT

Thermostat set too high.

Refer to HIGH TEMPERATURE REGULATION.

WATER HEATER SOUNDS

Condensation dripping on burner.

Refer to CONDENSATION above.

SIZZLING-RUMBLING

Sediment at bottom of heater tank.

Clean sediment from tank. Refer to DRAINING
instruction in Maintenance section of manual.

SOOTING

Improper combustion.

Refer to AIR REQUIREMENTS on page 4.

HEATER LIGHTS

Outlet polarity is reversed.

Test polarity and correct.

BUT GOES OUT

IN 4-5 SECONDS

Содержание GPSX-50L

Страница 1: ...installation and or operation of this water heater Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS CAUTION TEXT PRINTED OR OUTL...

Страница 2: ...45 When ordering parts provide complete model and serial numbers see rating plate quantity and name of part desired as listed in Figure 1 Standard hardware items may be purchased locally FIGURE1 N COL...

Страница 3: ...ep it on the side of the water heater or nearby for future reference Do obtain new warning and instruction labels for placement on the blanket directly over the existing labels Do inspect the insulati...

Страница 4: ...g jurisdiction In the absence of local codes the installation must comply with the current editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 The forme...

Страница 5: ...be suitable for use with potable water 2 Toxic chemicals such as those used for boiler treatment shall NEVER be introduced into this system 3 This unit may NEVER be connected to any existing heating...

Страница 6: ...3 1 NFPA54 7 3 4e and 7 8a b as follows 1 The exit terminals of a mechanical vent system shall be not less than 7 feet above grade when located adjacent to public walkways Figure 3 2 A venting system...

Страница 7: ...erminal to mount on the pipe Before the vent terminal is installed caulk not supplied around the pipe on the exterior wall and install the wall plate can be held to the outside wall by placing some of...

Страница 8: ...SERVICING THIS UNITIS MANUFACTURED WITHAN EXTERNALCONTROL HARNESS FOR EASIER REPLACEMENT IF THE HARNESS OR CONNECTORS GET DAMAGED Do not plug in power cord until vent system is completely installed Th...

Страница 9: ...ngs 4 The vent piping should be connected to the blower with a rubber adapter and secured with hose clamps The adapter and clamps are provided with the heater 5 Even though the flue gas temperature le...

Страница 10: ...ar the majority of failures in PVC and CPVC systems are the result of shortcuts and or improper joining techniques 2 SELECTIONOFMATERIALS Cutting Device Saw or Pipe Cutter Deburring Tool Knife File or...

Страница 11: ...fitting sockets and remove all dirt grease or moisture with a clean dry rag If wiping fails to clean the surfaces a chemical cleaner must be used Check for possible damage such as splits or cracks and...

Страница 12: ...ot water line Make sure that the insulation is against the top cover of the heater Fit T P valve insulation over valve Make sure that the insulation does not interfere with the lever of the T P valve...

Страница 13: ...LER and HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Tur...

Страница 14: ...you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing the point of use temperature by mixing cold and hot water are available...

Страница 15: ...Y INFORMATION SECTION FIRST USERS OF THIS APPLIANCE SHOULD BE AWARE THAT GAS COMPONENTS WEAR OUT OVER A PERIOD OF TIME THE GAS CARRYING COMPONENTS OFTHISAPPLIANCE SHOULD BE INSPECTED FOR PROPER OPERAT...

Страница 16: ...will damage the heater Turn off the gas and cold water inlet valve to the heater Open a nearby hot water faucet and the heater drain valve BE CAREFUL TO GRASP THE DRAIN VALVE HANDLE SO THAT THE HAND...

Страница 17: ...correct and secure 2 Replace hot surface ignitor System in lockout 1 Gas supply is off or too low to operate 2 Hot surface ignitor not positioned correctly 3 Low voltage to the water heater 4 Electric...

Страница 18: ...g and YELLOWFLAME air openings in bottom base pan for obstructions or blockage C Not enough dilution air for proper Check dilution air intake for obstructions combustion or blockage A Water on the flo...

Страница 19: ...empt to repair tank leaks or parts will void this warranty SERVICEANDLABORRESPONSIBILITY UNDERTHISLIMITEDWARRANTY THEWARRANTORWILLPROVIDE ONLYAREPLACEMENTWATERHEATERORPARTTHEREOF THEOWNER ISRESPONSIBL...

Страница 20: ...20 5621 W 115TH STREET ALSIP IL 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E mail parts hotwater com REPLACEMENT PARTS...

Отзывы: