background image

9

INSTALLATION OF VENT SYSTEM

  

 CAUTION

FOR INSTALLATION OF  A NEW VENT SYSTEM, FOLLOW THE
GUIDELINES IN THE MANUAL. FOR PRE-EXISTING VENT
SYSTEMS, INSPECT THE VENT FOR BLOCKAGE OR ANY SIGNS
OF DAMAGE. CHECK TO SEE IF THE VENT PIPE IS PROPERLY
PITCHED AND ITS JOINTS SECURED. FOLLOW THE VENTING
SPECIFICATIONS IN THIS MANUAL FOR THE RECOMMENDED
VENT MATERIAL, TERMINATION AND LOCATION.

(Refer to Figures 3, 4, 5, 7 and 8 as guides).

1. Plan the route of the vent system. Layout the total vent system to

use minimum of vent pipe and elbows. The vent piping may be
vented downward away from the blower per the required codes.
If the vent piping is sloped level or upwards away from the
blower, then adequate means for draining and disposing of
the condensate needs to be made by the installer, if condensate
is accumulating in the vent.

2. Refer to table above for allowable vent lengths.  Nonmetallic

vent piping may be used if it has a “Heat Deflection Temperature”
(HDT@66psi) of at least 157 degrees F.  Some typical
nonmetallic vent materials meeting this requirement are
schedule 40 PVC to ASTM D2665, schedule 40 CPVC to ASTM
D2846, and schedule 40 ABS to ASTM D2661.  The cement
used should be as recommended by the vent pipe
manufacturer.  The vent terminal provided is schedule 40 PVC
to ASTM D2665 and is a 2", 22.5 degree elbow. If the venting is
made with 3" or 4" pipe, the vent terminal must be a 3" or 4", 45
degree schedule 40 elbow (supplied locally). The supplied
screens for the 3" and 4" elbow must be used and installed
according to the provided instructions when one of these
terminals is used. If a material other than schedule 40 PVC is
used for venting, then an equivalent fitting of that material may
be substituted if the screen in the PVC terminal is removed and
inserted into the new fitting.  For water heaters installed in

locations with high ambient temperatures (above 100 degrees
F), it is recommended that schedule 40 CPVC or ABS be used.

3. See the instructions on pages 10 through 12  for  the proper

method of cutting and cementing the PVC pipe and fittings.

4. The vent piping should be connected to the blower with a

rubber adapter and secured with hose clamps.  The adapter
and clamps are provided with the heater.

5. Even though the flue gas temperature leaving the blower is

between 140°F and 175°F, some installations will have water
condense in the vent piping. If this occurs, then adequate
means of draining and disposing of the condensate needs to
be made by the installer.

FIGURE 7

The vent pipe may be installed with a slight downward slope
to drain condensate away from the blower.  The pipe may
slope 1/4 inch per five feet of pipe but not more than
1 1/2 inches in the total vent length.

The vent pipe should be properly supported and have
supports located no further apart than 5 feet on vertical runs
and 3 feet on horizontal runs.  All pipe and fittings should be
joined by the proper procedures discussed on pages 10 and
11 under the heading: VENT PIPE PREPARATION.

TABLE FOR VENT PIPE LENGTH 

TWO INCH DIAMETER PIPE 

**Number of 90º Elbows 

**Number of 45º Elbows 

Minimum Pipe 

Maximum Pipe 

One (1) 

None 

2 Ft. 

30 Ft. 

One (1) 

One (1) 

1 Ft. 

27.5 Ft. 

Two (2) 

None 

1 Ft. 

25 Ft. 

Two (2) 

One (1) 

1 Ft. 

22.5 Ft. 

Three (3) 

None 

1 Ft. 

20 Ft. 

Three (3) 

One (1) 

1 Ft. 

17.5 Ft. 

Four (4) 

None 

1 Ft. 

15 Ft. 

THREE INCH DIAMETER PIPE 

**Number of 90º Elbows 

**Number of 45º Elbows 

Minimum Pipe 

Maximum Pipe 

One (1) 

None 

2 Ft. 

65 Ft. 

One (1) 

One (1) 

2 Ft. 

62.5 Ft. 

Two (2) 

None 

1 Ft. 

60 Ft. 

Two (2) 

One (1) 

1 Ft. 

57.5 Ft. 

Three (3) 

None 

1 Ft. 

55 Ft. 

Three (3) 

One (1) 

1 Ft. 

52.5 Ft. 

Four (4) 

None 

1 Ft. 

50 Ft. 

Four (4) 

One (1) 

1 Ft. 

47.5 Ft. 

***Five (5) 

None 

1 Ft. 

45 Ft. 

***Five (5) 

One (1) 

1 Ft. 

42.5 Ft. 

***Six (6) 

None 

1 Ft. 

40 Ft. 

FOUR INCH DIAMETER PIPE 

**Number of 90º Elbows 

**Number of 45º Elbows 

Minimum Pipe 

Maximum Pipe 

One (1) 

None 

2 Ft. 

90 Ft. 

One (1) 

One (1) 

2 Ft. 

87 Ft. 

Two (2) 

None 

1 Ft. 

83 Ft. 

Two (2) 

One (1) 

1 Ft. 

79 Ft. 

Three (3) 

None 

1 Ft. 

75 Ft. 

Three (3) 

One (1) 

1 Ft. 

71 Ft. 

 

**

One (1) 90º elbow is equal to two (2) 45º elbows.

*** It is not recommended that more than (4) 90º elbows be used, or a combination of three (3) 90º and two (2) 45º elbows, but as long as the

total length is less than in the chart above, the vent system is acceptable.

Note: For the two inch and three inch vent, one (1) 90º is approximately the same as five (5) feet of pipe. For the four inch vent, one (1) 90º

elbow is approximately the same as eight (8) feet of pipe.

Содержание GPSX-50L

Страница 1: ...installation and or operation of this water heater Please pay particular attention to the important safety and operating instructions as well as the WARNINGS and CAUTIONS CAUTION TEXT PRINTED OR OUTL...

Страница 2: ...45 When ordering parts provide complete model and serial numbers see rating plate quantity and name of part desired as listed in Figure 1 Standard hardware items may be purchased locally FIGURE1 N COL...

Страница 3: ...ep it on the side of the water heater or nearby for future reference Do obtain new warning and instruction labels for placement on the blanket directly over the existing labels Do inspect the insulati...

Страница 4: ...g jurisdiction In the absence of local codes the installation must comply with the current editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 The forme...

Страница 5: ...be suitable for use with potable water 2 Toxic chemicals such as those used for boiler treatment shall NEVER be introduced into this system 3 This unit may NEVER be connected to any existing heating...

Страница 6: ...3 1 NFPA54 7 3 4e and 7 8a b as follows 1 The exit terminals of a mechanical vent system shall be not less than 7 feet above grade when located adjacent to public walkways Figure 3 2 A venting system...

Страница 7: ...erminal to mount on the pipe Before the vent terminal is installed caulk not supplied around the pipe on the exterior wall and install the wall plate can be held to the outside wall by placing some of...

Страница 8: ...SERVICING THIS UNITIS MANUFACTURED WITHAN EXTERNALCONTROL HARNESS FOR EASIER REPLACEMENT IF THE HARNESS OR CONNECTORS GET DAMAGED Do not plug in power cord until vent system is completely installed Th...

Страница 9: ...ngs 4 The vent piping should be connected to the blower with a rubber adapter and secured with hose clamps The adapter and clamps are provided with the heater 5 Even though the flue gas temperature le...

Страница 10: ...ar the majority of failures in PVC and CPVC systems are the result of shortcuts and or improper joining techniques 2 SELECTIONOFMATERIALS Cutting Device Saw or Pipe Cutter Deburring Tool Knife File or...

Страница 11: ...fitting sockets and remove all dirt grease or moisture with a clean dry rag If wiping fails to clean the surfaces a chemical cleaner must be used Check for possible damage such as splits or cracks and...

Страница 12: ...ot water line Make sure that the insulation is against the top cover of the heater Fit T P valve insulation over valve Make sure that the insulation does not interfere with the lever of the T P valve...

Страница 13: ...LER and HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Tur...

Страница 14: ...you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing the point of use temperature by mixing cold and hot water are available...

Страница 15: ...Y INFORMATION SECTION FIRST USERS OF THIS APPLIANCE SHOULD BE AWARE THAT GAS COMPONENTS WEAR OUT OVER A PERIOD OF TIME THE GAS CARRYING COMPONENTS OFTHISAPPLIANCE SHOULD BE INSPECTED FOR PROPER OPERAT...

Страница 16: ...will damage the heater Turn off the gas and cold water inlet valve to the heater Open a nearby hot water faucet and the heater drain valve BE CAREFUL TO GRASP THE DRAIN VALVE HANDLE SO THAT THE HAND...

Страница 17: ...correct and secure 2 Replace hot surface ignitor System in lockout 1 Gas supply is off or too low to operate 2 Hot surface ignitor not positioned correctly 3 Low voltage to the water heater 4 Electric...

Страница 18: ...g and YELLOWFLAME air openings in bottom base pan for obstructions or blockage C Not enough dilution air for proper Check dilution air intake for obstructions combustion or blockage A Water on the flo...

Страница 19: ...empt to repair tank leaks or parts will void this warranty SERVICEANDLABORRESPONSIBILITY UNDERTHISLIMITEDWARRANTY THEWARRANTORWILLPROVIDE ONLYAREPLACEMENTWATERHEATERORPARTTHEREOF THEOWNER ISRESPONSIBL...

Страница 20: ...20 5621 W 115TH STREET ALSIP IL 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E mail parts hotwater com REPLACEMENT PARTS...

Отзывы: